Item
Description
1
Local Display
2
Communication Port on Local Display
3
One of Four Screws Securing Local Display to the Vertiv™ VR Door
4
Local Display Cable Connected to Rear of Vertiv VRC
5
RJ-45-to-USB Cable between Geist™ rPDU and Vertiv™ VRC
Table 4.3 Display Cable Attachment and Connections Descriptions
4.8.1 Route Display, Fan Cables
The cables for the local display and fan must be routed along the upper edge of the door and down the rack rail to protect
them from damage and strain when the rear door is opened and closed. Cable ties with a special clip are factory-supplied
to attach the cables to the door lip and the rack rail.
WARNING! Risk of electric shock. Can cause property damage, injury and death. The backup
fan input power cable is a live wire when connected. Pulling it loose from the connector or
abrading it on the rack may expose personnel to hazardous voltage. When routing the cable, be
sure to leave enough slack in the cables to permit the door to open fully without straining the
cables' connections.
To route the cables for the local display and the fan:
1.
Open the rear door of the Vertiv™ VRC-S.
2.
Route the local display and fan cables around the outside edge of the fan housing and up to the top of the door.
3.
Use a factory-supplied cable tie to bundle the two cables as shown in Figure 4.7 on the next page and as
detailed below.
a. Place the cables against the pad on the cable tie.
IMPORTANT! The cables must be properly placed in the cable tie so they can be positioned under the
lip of the door for protection against pinching.
b. Slip the longer end around the cables and through the ratcheted end of the cable tie.
c. Pull the cable tie until it is snug around the cables.
d. Snip off the excess cable to ease attachment to the door.
4. Leaving adequate slack in the cables, press the clip onto the top inner edge of the rear door as shown in Figure
4.7 on the next page . The cables should be under the door's lip to prevent pinching.
5.
Repeat 3 to attach at least one more cable tied bundle near the hinged edge of the door.
6. Leaving adequate slack in the cables for the door to open, secure the cables to the rack rail near the Geist™
rPDU.
7.
Secure the cables to the rack rail as needed for good cable management.
4 Installation
27
Vertiv™| VRC-S User Manual
Содержание VRC-S
Страница 1: ...VRC S User Manual...
Страница 10: ...1 Important Safety Instructions 6 This page intentionally left blank Vertiv VRC S User Manual...
Страница 20: ...2 Introduction 16 This page intentionally left blank Vertiv VRC S User Manual...
Страница 38: ...5 Operation 34 This page intentionally left blank Vertiv VRC S User Manual...
Страница 64: ...9 Appendices 60 This page intentionally left blank Vertiv VRC S User Manual...
Страница 65: ...Vertiv VRC S User Manual...