8 Specifications
8.1 Vertiv™ VRC-S with VRC self-contained 120V NAM
VRC-S SKUs
VRCS3350-120V
VRCS3300-120V
VRCS3307-120V
VRCS3357-120V
Configured system weight
319 kg (704 lb.)
274 kg (605 lb.)
310 kg (684 lb.)
337 kg (743 lb.)
Shipping weight
419 kg (924 lb.)
361 kg (796 lb.)
397 kg (876 lb.)
437 kg (964 lb.)
Sound (at 60% fan speed and 40% compressor speed)
52.5 dBA @ 1 m
52.5 dBA @ 1 m
52.5 dBA @ 1 m
52.5 dBA @ 1 m
Rack dimensions U; H, W, D
42U; 2000 mm, 800
mm, 1200 mm (78.6
in., 31.5 in., 47.8 in.)
42U; 2000 mm, 600
mm, 1200 mm (78.6
in., 23.6 in., 47.8 in.)
48U; 2200 mm, 600
mm, 1200 mm (86.6
in., 23.6 in., 47.8 in.)
48U; 2200 mm, 800
mm, 1200 mm (86.6
in., 31.5 in., 47.8 in.)
Usable space available for IT equipment
32U
32U
38U
38U
Shipping weight of rack
N /A
N /A
N /A
N /A
Shipping dimensions of rack H, W, D
2134 mm, 826 mm,
1385 mm(84 in., 32.5
in., 54.5 in.)
2134 mm, 626 mm,
1385 mm(84 in., 24.6
in., 54.5 in.)
2396 mm, 626 mm,
1385 mm (94.3 in.,
24.6 in., 54.5 in.)
2396 mm, 826 mm,
1385 mm (94.3 in.,
32.5 in., 54.5 in.)
rPDU (Pre-installed in rack)
NU30021
rPDU sub-type
Switched
rPDU type
Outlet Level Monitoring
Voltage
120 V
Input current
30 A
Regulatory derated input current (North America)
24 A
rPDU rated maximum
2.8 kW
Horizontal/Vertical
Vertical
rPDU input plug
NEMA L5-30P
Cord length
3 m
Outlets
(24) NEMA 5-20R
NOTE: (2) NEMA 5-20R outlets will be required and preprogrammed for the
backup fan and condensate pump.
Vertiv Intelligence Director enabled
YES
Geist Upgradable 2.0 protocols supported
ARP, IPv4, IPv6, ICMP, ICMPv6, NDP, TCP, UDP, RSTP, STP, DNS, HTTP, HTTPS (TLSv1.2),
SMTP, SMTPS, DHCP, SNMP (v1/v2c/v3), LDAP, NTP, SSH, and Syslog
Certifications/Agency approvals
UL & c-UL Listed 60950, RoHS Compliant, FCC Part 15 Class A Conformance
Cooling Kit Type
VRC100KIT
Cooling capacity
0.9 - 3.5 kW
Air Volume
750 m³/h
VRC Input plug
NEMA 5-20P
Cord length
3.2 m (10ft)
8 Specifications
41
Vertiv™| VRC-S User Manual
Содержание VRC-S
Страница 1: ...VRC S User Manual...
Страница 10: ...1 Important Safety Instructions 6 This page intentionally left blank Vertiv VRC S User Manual...
Страница 20: ...2 Introduction 16 This page intentionally left blank Vertiv VRC S User Manual...
Страница 38: ...5 Operation 34 This page intentionally left blank Vertiv VRC S User Manual...
Страница 64: ...9 Appendices 60 This page intentionally left blank Vertiv VRC S User Manual...
Страница 65: ...Vertiv VRC S User Manual...