DIAGNOSTICS
Vertical Express Product Manual
3-35
88500 v.1.0
Diagnostics Section
Control System Fault Codes
This manual shows only the parameters that have an operational relevance to the ICON32. The UIT may have
additional parameters available, which should not effect the controller operation.
1049
Open door protection failure - The doors failed to open in the
allotted time.
• A defective I/O.
• A defective door operation.
1050
Close door protection failure - The doors failed to close in the
allotted time.
• A defective I/O.
• A defective door operation.
1051
Stuck door opening device error - The SE, EE, DOB, or DHB I/
O is stuck in the active state.
• A defective I/O.
• A defective door operation.
1052
Stuck DCB error - A DCB I/O is stuck in the active state.
• A defective I/O.
• A defective door operation.
1053
The Fire Service Phase 1 secondary switch I/O does not
match the adjustment.
• An invalid adjustment F16 for fire service type.
• An invalid adjustment F15 for the secondary fire service
switch type.
• The I/O provided does not match requirements.
1054
Down run time has exceeded 5 minutes - The down run
request was longer than the time allowed for a full hoistway
run in the down direction.
• A defective valve adjustment.
• A defective valve.
1056
Floor tables of the encoder counts are not set up when
attempting an auto run. When the elevator is not on inspec-
tion operation, and the level reference in non-volatile mem-
ory for any floor is invalid.
• A defective hoistway scan.
• A defective CPU.
• A defective CPU battery.
• Loose battery connections.
• An improper power unit setup.
• Improper selector signals.
• Verify the Position and/or Motion adjustments.
1057
The encoder is out of tolerance at the floor level - The car is
at floor level, and the encoder position count is different than
the floor position count by more than the value in adjustment
P20.
• A defective encoder.
1058
Selector position wrong at limit of travel - The car is at the
bottom or top of its travel limit and the selector has deter-
mined that the closest floor is not the corresponding bottom
or top floor.
—
1059
Bad encoder re-calibration - Two consecutive encoder re-cal-
ibrations were out of range. The encoder reported a count
(while at two consecutive floors) that was different from each
floor position count by more than adjustment P20.
• A defective encoder.
1060
The selector setup was not completed - The selector setup
either failed or was terminated before completion.
• Other system fault interrupted the setup.
• A defective CPU.
• A defective selector
1061
Selector setup position count table error - The setup has
determined that a value for a floor was invalid, and the setup
is invalidated.
• A defective selector.
• Wrong number of floors in the job image.
• Wrong job image.
Code
Description
(cont.)
Possible Causes/Solutions
(cont.)
Содержание ICON 32
Страница 1: ...Controller...
Страница 3: ...INSTALLATION SECTION...
Страница 4: ...INSTALLATION SECTION...
Страница 39: ...ADJUSTMENT SECTION...
Страница 40: ...ADJUSTMENT SECTION...
Страница 42: ...2 2 Vertical Express Printed in USA April 2020 Contents Adjustment Section This page intentionally left blank...
Страница 83: ...DIAGNOSTICS SECTION...
Страница 84: ...DIAGNOSTICS SECTION...
Страница 86: ...3 2 Vertical Express Printed in USA April 2020 Contents Diagnostics Section This page intentionally left blank...
Страница 131: ...TROUBLESHOOTING SECTION...
Страница 132: ...TROUBLESHOOTING SECTION...
Страница 134: ...4 2 Vertical Express Printed in USA April 2020 Contents Troubleshooting Section This page intentionally left blank...
Страница 165: ...SERVICE INFORMATION SECTION...
Страница 166: ...SERVICE INFORMATION SECTION...
Страница 168: ...5 2 Vertical Express Printed in USA April 2020 Contents Service Section This page intentionally left blank...
Страница 205: ...REFERENCE SECTION SERVICE REFERENCE SECTION...
Страница 206: ...REFERENCE SECTION...
Страница 208: ...5R 2 Vertical Express Printed in USA April 2020 Contents Reference Section This page intentionally left blank...