7
20307393
5" x 8" DVP Termination Kit
DVP-RVTK, DVP-RVTM, DVP-HVTK
HORIZONTAL TERMINATION KIT
Installation Instructions
Figure 12
1.
KHLDV, KSTDV & VWDV FIREPLACES REQUIRED
:
Attach 24" (610 mm) fixed-length pipe to the starting
collar on the unit.
WDV REQUIRED:
Attach 12" (305 mm) fixed-length
pipe to the starting collar on the unit.
2. a.
DVP-HVTK ONLY:
Attach the 90° elbow to the pipe
connector (or 24" pipe). See page 3 for directions on
how pipe and elbows are connected.
b.
DVP-RVTK & DVP-RVTM ONLY:
Determine final
location of termination cap.
KT1492
horizontal term kit
90° Elbow
Adjustable Pipe
Firestop
Termination
Cap
Fireplace
DVP-HVTK
DVP-RVT12AM
Pipe
Firestop
Fireplace
KT1492
Termination Cap
DVP-RVTM uses adjustable pipe instead of
cut-to-length.
KHLDV/KSTDV/VWDV must
use 24" fixed-length pipe,
installed before the 90° elbow.
Figure 12 Installation of Horizontal Termination Kit
DVP-RVTM
3. a.
DVP-RVTK, DVP-RVTM, DVP-HVTK:
Attach the
adjustable pipe to the pipe connector (or elbow).
See page 3 for directions on how pipe and elbows
are connected.
b.
DVP-RVTM, DVP-HVTK:
During shipping, the
DVP6A is slid over the DVP6 to make an adjustable
pipe. In some installations, you may want to use
only the DVP6 (for instances in which the adjust-
able pipe is too long for installation.) Otherwise,
adjust pipe to desired length.
4. A wall square firestop
MUST BE
installed if the vent
passes through a ceiling or exterior combustible wall.
Cut a 10" wide x 10" high (254 x 254 mm) opening
through the wall or framing. A wall rectangular firestop
MUST BE
installed if the vent passes through interi-
or walls. In that case, cut a 10" wide x 12" high (254
x 305 mm) opening through the wall or framing. The
framing members may need to be reinforced. Position
the firestop on the hole previously cut and secure with
screws or nails (not provided). Run vent pipe through
firestop. The gap between the vent pipe and the
firestop may be sealed.
5. Attach slip section of cap to last vent section. Maintain
1
1
⁄
2
in. overlap between slip and vent sections. Make
sure the termination cap is installed with embossed ar-
row pointing up.
6. If the house has vinyl siding, mark and cut the vinyl
siding around the pipe so the termination cap can be
mounted flush to the wall. Finish the siding edges with
trim or "J channel" and caulking to prevent water from
leaking into the building.
Figure 13
7. Attach the termination cap to the exterior wall using
the four (4) screws provided.
NOTE: You may use the DVP-RVTK OR DVP-RVTM
for corner installations. You may also use the
DVP45M off the rear of the unit witha 45° elbow
(p/n 1245) and proper length of pipe(s). Refer to
appropriate venting charts in appliance installation
manual.
WDV must use 12" fixed-
length pipe, installed before
the 90° elbow.