4
20307393
5" x 8" DVP Termination Kit
Figure 4 Snapped
Assemble Slip Sections
The outer flue of the slip section should slide over the outer
flue of the pipe section and into (inner flue) the last pipe
section (see Figure 5) .
Slide together to the desired length, making sure that a
1-1/2 in. outer flue overlap is maintained between the pipe
section and slip section.
The pipe and slip section need to be secured by driving
two screws through the overlapping portions of the outer
flues using the pilot holes (see Figure 6).
This will secure the slip section to the desired length and
prevent it from separating. The slip section can then be
attached to the next pipe section.
If the slip section is too long, the inner and outer flues of
the slip section can be cut to the desired length.
CORRECT
INCORRECT
Make sure the seams are not aligned to prevent unintention-
al disconnection.
Figure 5 Slip Section Pilot Holes
Figure 6 Screws into Slip Section
WARNING
Risk of Fire/Explosion!
DO NOT
break seals on slip
sections. Use care when removing termination cap from
slip pipe. If slip section seals are broken during removal
of the termination cap, vent may leak.
WARNING
Fire Risk
Exhaust Fumes Risk
•
Overlap pipe slip sections at least 1-1/2 inches.
•
Use pilot holes for screws.
•
Screws must not exceed 1 in. long.
•
Pipe may separate if not properly joined.