8
20307393
5" x 8" DVP Termination Kit
KT1493
cap on sidingT
Cutout On Vinyl
Vinyl Siding Wall
Termination Cap
Figure 13 Horizontal Termination Cap on a Vinyl Siding Wall
DVP-HSFTK -
HORIZONTAL TERMINATION KIT
Figure 14
Installation Instructions
1. 1. Set the unit in place and survey how best to vent
the unit.
2. A wall square firestop
MUST BE
installed if the vent
passes through a ceiling or exterior wall. Cut a 10"
wide x 10" high (254 x 254 mm) opening through the
exterior wall or framing. A wall rectangular firestop
(not provided)
MUST BE
installed if the vent passes
through interior walls. In that case, cut a 10" wide x
12" high (254 x 305 mm) opening through the wall or
framing. The framing members may need to be rein
-
forced. Position the firestop on the hole previously cut
and secure with screws or nails (not provided). Run
vent pipe through firestop. The gap between the vent
pipe and firestop may be sealed.
3. If the house has vinyl siding, after the termination cap
location has been decided, mark and cut the vinyl sid-
ing around the termination cap so that the cap can be
mounted flush to the wall.
4. Attach the DVP flex starter onto the starting collar on
the unit. Slide the male end of the inner flue over the
inner collar of the appliance, at the same time, slide
the outer flue over the outer collar of the appliance.
Push the flex starter section into the appliance collar
until all the lances have snapped in place. Tug slight
-
ly on the section to confirm it has completely locked
into place. Install three (3) self tapping #10 screws
through the DVP flex starter into the starting collar of
the appliance.
5. Slide one end of the 5" flex pipe over the inner pipe of
the DVP flex starter that is attached to the unit. Se
-
cure the flex pipe to the inner of the DVP flex starter
with one (1) small band clamp and three (3) self tap-
ping #10 screws.
Termination Cap with
slip section
DVP Inner Flex
Adapter
DVP Outer Flex
Adapter
Flex Pipe 5” x 48”
Flex Pipe 8” x 48”
Small Hose Clamp
Large Hose Clamp
Screws
Spacer Spring
Exhaust Pipe
Starting Collar
(on unit)
DVP Flex Starter
Figure 14 DVP-HSFTK
WARNING
Refer to your fireplace Homeowner’s Manual for the
minimum and maximum venting requirements of your
fireplace and for approved horizontal vent termination
locations prior to installation. Failure to do so may cause
fire hazard.
WARNING
Any horizontal run must have a 1/4" rise for every one
(1) foot of run towards the vent termination. Never
allow the vent pipe to run down. This could cause high
temperatures and may present a fire hazard.
WARNING
Termination cap must be positioned so the embossed
arrow is pointed up.
WARNING
This flexible pipe termination kit is ONLY for horizontal
terminations with one (1) 90° bend.