16
20306744
WDV Series Gas Fireplace
VENTING INSTALLATION
Example:
Elbow 1 = 90°
Elbow 2 = 45°
Elbow 3 = 45°
Elbow 4 = 90°
Total Angular Variation = 270°
Figure 17 -
Maximum Elbow Usage
1
2
3
4
1
2
3
4
FP1180
max bends
12"
Minimum
FP1180
BELOW GRADE INSTALLATIONS
When it is not possible to meet the required vent terminal
clearances of 12" above grade level, a snorkel kit is rec-
ommended. It allows installation depth down to 7" (178
mm) below grade level. The 7" (178 mm) is measured
from the center of the horizontal vent pipe as it penetrates
through the wall.
Ensure that sidewall venting clearances are observed.
If venting system is installed below ground, we recom
-
mend a window well with adequate and proper drainage
to be installed around the termination area.
If installing a snorkel, a minimum 12" vertical rise is neces-
sary. The maximum horizontal run with the 12” vertical pipe
is 36". This measurement is taken from the collar of the
fireplace (or transition elbow) to the face of the exterior wall.
See the Sidewall Venting Graph for extended horizontal
run if the vertical exceeds 12".
1. Establish vent hole through the wall.
2. Remove soil to a depth of approximately 16" below base
of snorkel. Install drain pipe. Install window well (not
supplied). Refill hole with 12" of coarse gravel leaving
a clearance of approximately 4" below snorkel.
Figure
18
3. Install vent system.
4. Ensure a watertight seal is made around the vent pipe
coming through the wall.
5. Apply high temperature sealant caulking (supplied)
around the 5" and 8" snorkel collars.
6. Slide the snorkel into the vent pipes and secure to the
wall.
7. Level the soil so as to maintain a 4" clearance below
snorkel.
Figure 18
FP2134
below grade install
FP2134
Figure 18 -
Below Grade Installation
Screws
Minimum
4" Clearance
Ground
Window
Well
Gravel
Drain
Foundation Wall
Firestop
12"
Minimum
If the foundation is recessed, use recess brackets (not
supplied) for securing lower portion of the snorkel. Fasten
brackets to wall first, then secure to snorkel with self drilling
#8 x 1/2" sheet metal screws. It will be necessary to extend
vent pipes out as far as the protruding wall face.
Figure 19
FP1966
snorkel
Figure 19 -
Snorkel Installation, Recessed Foundation
Foundation
Recess
Watertight Seal
Around Pipe
Sheet Metal
Screws
Wall Screws
Snorkel
W
ARNING
• Do not back fill around snorkel.
• A clearance of at least 4" must be
maintained between the snorkel
and the soil.
For models purchased after 4/16/15, please see addendum.