6
20307393
5" x 8" DVP Termination Kit
Attach slip section of cap to last vent section. Maintain 1-1/2
in. overlap between slip and vent sections.
Secure termination cap to exterior wall using provided
holes and fasteners.
Vent termination must not be recessed in the wall. Siding
may be brought to the edge of the cap base.
Flash and seal as appropriate for siding material at outside
edges of cap.
When installing a horizontal termination cap, follow the cap
location guidelines as prescribed by current ANSI Z223.1
and CAN/CGA-B149 installation codes.
Divert Roof Run-off
VCG/HHT recommends, where excessive water run-off
is possible, use of one of the two options shown below
to prevent water running off the roof and onto/into the
horizontal termination cap.
Install gutter
Install L-shaped
diverter
Figure 11 Divert Roof Run-off