AC70T Crane Purpose VFD Manual
53
Translation mechanism dedicated macro
NO.
Function description
Range of settings and definition
Factory
default
F0.00
Motor control mode
Open loop vector control mode 1
0
F0.02
Run command channel
Terminal control
1
F0.03
Frequency given source
channel A
Keyboard number given
0
F0.08
Keyboard number setting
frequency
0
~
upper limit
20.00Hz
F0.14
ACC time 1
0.01
~
650.00s
3.0s
F0.15
DEC time 1
0.01
~
650.00s
3.0s
F2.00
Multifunction input
terminal 1(X1)
FWD
1
F2.01
Multifunction input
terminal 2(X2)
REV
2
F2.02
Multifunction input
terminal 3(X3)
Malfunction reset
8
F2.03
Multifunction input
terminal 4(X4)
Multispeed terminal 1
16
F2.04
Multifunction input
terminal 5(X5)
Multispeed terminal 2
17
F2.05
Multifunction input
terminal 6(X6)
Multispeed terminal 3
18
F2.06
Multifunction input
terminal 7(X7/PUL)
Multispeed terminal 4
19
F2.45
Output terminal 1
The inverter is running
1
F2.46
Relay output 1
Fault trip alarm1
4
F2.47
Relay output 2
The inverter is running
1
FC.00
PLC Speed 1
0.00
~
Max frequency
35.00Hz
FC.02
PLC Speed 3
0.00
~
Max frequency
50.00Hz
FC.06
PLC Speed 7
0.00
~
Max frequency
40.00Hz
FC.14
PLC Speed 15
0.00
~
Max frequency
50.00Hz
Fd.07
Modbus communication
fault action mode
selection
No checkout overtime fault
0
FF.00
Application type selection
Translation mechanism
2