AC70T Crane Purpose VFD Manual
26
F3.00
VS Lower limit
0.00-10.00V
0.00V
●
0x300
F3.01
VS Lower limit
corresponding setting
-100.00-100.00%
0.00%
●
0x301
F3.02 VS
upper
limit
0.00-10.00V
10.00V
●
0x302
F3.03
VS upper limit
corresponding setting
-100.00-100.00%
100.00%
●
0x303
F3.04 VS
filter
time
0.00-6.00s
0.010s
●
0x304
F3.05
VS zero point loop
voltage
0.00-10.00V
0.00V
●
0x305
F3.06
AI( VS) lower limit
0.00-10.00V
0.00V
●
0x306
F3.07
AI (VS)lower limit
corresponding setting
0.00-100.00%
0.00%
●
0x307
F3.08
AI used as VS upper
0.00-10.00V
10.00V
●
0x308
F3.09
AI (VS)upper limit
corresponding setting
0.00-100.00%
100.00%
●
0x309
F3.10
AI filter time
0.00-6.00s
0.010s
●
0x30A
F3.11 AS
lower
limit
0.00-20.00mA
4.00mA
●
0x30B
F3.12
AS lower limit
corresponding setting
0.00-100.00%
0.00%
●
0x30C
F3.13 AS
upper
limit
0.00-20.00mA
20.00mA
●
0x30D
F3.14
AS upper limit
corresponding setting
0.00-100.00%
100.00%
●
0x30E
F3.15
AS filter time
0.000-6.000s
0.010s
●
0x30F
F3.16
AI used as AS lower limit
0.00-20.00mA
4.00mA
●
0x310
F3.17
AI ( AS) lower limit
corresponding setting
0.00-100.00%
0.00%
●
0x311
F3.18
AI used as AS lower limit
0.00-20.00mA
20.00mA
●
0x312
F3.19
AI ( AS) upper limit
corresponding setting
0.00-100.00%
100.00%
●
0x313
F3.20
Vs terminal function
selection (used as X)
See X terminal function
0
〇
0x314
F3.21
VS high level setting
0.00-100.00%
70.00%
●
0x315
F3.22
VS low level setting
0.00-100.00%
30.00%
●
0x316
F3.23
AI terminal function
selection (used as X)
See X terminal function
0
〇
0x317
F3.24
AI high level setting
0.00
~
100.00%
70.00%
●
0x318
F3.25
AI low level setting
0.00
~
100.00%
30.00%
●
0x319
F3.26
AS terminal function
selection (as X)
See X terminal function
0
〇
0x31A
F3.27
AS high level setting
0.00
~
100.00%
70.00%
●
0x31B
F3.28
AS low level setting
0.00
~
100.00%
30.00%
●
0x31C