Commissioning
Function "range of mapping" (052)
This function displays the suggested range of mapping. The reference point is always
the reference point of the measurement (see page 46). This value can be edited by the
operator.
For manual mapping, the default value is: 0 m.
Function "start mapping" (053)
This function is used to start the interference echo mapping up to the distance given in
"
range of mapping
"
(052)
.
Selection:
•
off
: no mapping is carried out
• on: mapping is started
⇒
E
+
–
⇒
E
+
–