Commissioning
Radar Tank Gauge
52
Installation and Operations Manual
Function "empty calibr." (005)
This function is used to enter the distance from the flange (reference point of the
measurement) to the minimum level (=zero).
Caution!
For dish bottoms or conical outlets, the zero point should be no lower than the point at
which the radar beam hits the bottom of the tank.
Function "full calibr." (006)
This function is used to enter the distance from the minimum level to the maximum level
(=span).
In principle, it is possible to measure up to the tip of the antenna. However, due to
considerations regarding corrosion and build-up, the end of the measuring range
should not be chosen any closer than 50 mm (2”) to the tip of the antenna.
⇒
E
+
–
L0
0-
FM
R2xxx
x-
14
-0
0-
06
-e
n-
00
8
⇒
E
+
–
L00-F
M
R2
xxxx-14
-00
-0
6-en-00
9
Содержание 7532
Страница 21: ...21 7532 Mounting Preparation for the installation of the Varec UNI flange R532xx 00 00 06 en 002...
Страница 31: ...31 7532 Operation 5 Operation 5 1 Quick operation guide...
Страница 44: ...Operation Radar Tank Gauge 44 Installation and Operations Manual...
Страница 46: ...Commissioning Radar Tank Gauge 46 Installation and Operations Manual 6 3 Basic Setup...
Страница 72: ...Commissioning Radar Tank Gauge 72 Installation and Operations Manual...
Страница 74: ...Maintenance Radar Tank Gauge 74 Installation and Operations Manual...
Страница 76: ...Accessories Radar Tank Gauge 76 Installation and Operations Manual...
Страница 77: ...77 7532 Troubleshooting 9 Troubleshooting 9 1 Troubleshooting instructions...
Страница 91: ...91 7532 Appendix 11 Appendix 11 1 Operating menu HART Display modul ToF Tool...
Страница 94: ...Appendix Radar Tank Gauge 94 Installation and Operations Manual 11 2 Operating matrix HART Commuwin II...
Страница 105: ...7532 IOM027FVAE0804 105 Notes...