51
7532
Commissioning
Function "process cond." (004)
This function is used to select the process conditions.
Selection:
•
standard
• calm surface
• turb. surface
• agitator
• fast change
• test:no filter
Note!
The phase evaluation of the 7500 RTG (see »Function "auto-correction" (031)« on
page 57) is only activated if you select the measuring conditions "
standard
" or
"
calm surface
". We strongly recommend that, in the case of rough product surfaces or
rapid filling, you activate the appropriate application parameters.
⇒
E
+
–
standard
calm surface
For all applications that do
not fit into any of the
following groups.
Storage tanks with immersion
tube or bottom filling
The filter and output
damping are set to average
values.
The averaging filters and
output damping are set to
high values.
-> steady meas. value
-> precise measurement
-> slower reaction time
Содержание 7532
Страница 21: ...21 7532 Mounting Preparation for the installation of the Varec UNI flange R532xx 00 00 06 en 002...
Страница 31: ...31 7532 Operation 5 Operation 5 1 Quick operation guide...
Страница 44: ...Operation Radar Tank Gauge 44 Installation and Operations Manual...
Страница 46: ...Commissioning Radar Tank Gauge 46 Installation and Operations Manual 6 3 Basic Setup...
Страница 72: ...Commissioning Radar Tank Gauge 72 Installation and Operations Manual...
Страница 74: ...Maintenance Radar Tank Gauge 74 Installation and Operations Manual...
Страница 76: ...Accessories Radar Tank Gauge 76 Installation and Operations Manual...
Страница 77: ...77 7532 Troubleshooting 9 Troubleshooting 9 1 Troubleshooting instructions...
Страница 91: ...91 7532 Appendix 11 Appendix 11 1 Operating menu HART Display modul ToF Tool...
Страница 94: ...Appendix Radar Tank Gauge 94 Installation and Operations Manual 11 2 Operating matrix HART Commuwin II...
Страница 105: ...7532 IOM027FVAE0804 105 Notes...