59
7532
Commissioning
Display "custody mode" (0A9)
This indicates the instrument calibration mode. The calibration mode (active) can be set
using the hardware security lock on the electronics (see Page 34).
Selection:
• inactive
• active pos.
• active neg.
active pos.
The custody mode (instrument is lead-sealed and accurate to the nearest mm) is active
and is held.
active neg.
Custody mode (instrument is lead-sealed and accurate to the nearest mm) is activated
and not held, e.g. because the signal-to-noise ratio is less than 10 dB (refer to
function "
echo quality
"
(056)
in the function group "
extended calibr.
"
(05)
).
Caution!
After entering all the values and completing mounting and aligning work, enter the
Reset Code "
555
" in the function
"
history reset
"
(009)
of the "
basic setup
"
(00)
function
group to reset the instrument history for auto-correction.
⇒
E
+
–
Содержание 7532
Страница 21: ...21 7532 Mounting Preparation for the installation of the Varec UNI flange R532xx 00 00 06 en 002...
Страница 31: ...31 7532 Operation 5 Operation 5 1 Quick operation guide...
Страница 44: ...Operation Radar Tank Gauge 44 Installation and Operations Manual...
Страница 46: ...Commissioning Radar Tank Gauge 46 Installation and Operations Manual 6 3 Basic Setup...
Страница 72: ...Commissioning Radar Tank Gauge 72 Installation and Operations Manual...
Страница 74: ...Maintenance Radar Tank Gauge 74 Installation and Operations Manual...
Страница 76: ...Accessories Radar Tank Gauge 76 Installation and Operations Manual...
Страница 77: ...77 7532 Troubleshooting 9 Troubleshooting 9 1 Troubleshooting instructions...
Страница 91: ...91 7532 Appendix 11 Appendix 11 1 Operating menu HART Display modul ToF Tool...
Страница 94: ...Appendix Radar Tank Gauge 94 Installation and Operations Manual 11 2 Operating matrix HART Commuwin II...
Страница 105: ...7532 IOM027FVAE0804 105 Notes...