geoTHERM exclusive VWS 0020051614_00 installation instructions
6.4.3 Dual circuit feed, special tariff
(Electroplan 3)
L
N
S
S B B
L
L
:
:
2 kW
4 kW
PE
PE
L
L
N
N
L
L
N
N
N
L
N
L
+
+
1
2
3
230 V / 50 Hz
230 V / 50 Hz
Fig. 6.4 Dual circuit feed, special tariff
Key to Fig. 6.4
Pump
Compressor
Controller
Auxiliary heater
:
:
2 kW
4 kW
Alternatively, you can set the aux-
iliary heating from 4 kW to 2 kW
power by disconnecting the bridg-
ing line.
In this instance the heat pump is operated on two tariffs
(two consumer meters). A permanent supply (
2
) for the
secondary consumers (circulation pumps, controller,
etc.)
must be ensured via a meter. The
low tariff sup-
ply (1) for the compressor and the auxiliary heating
is
effected via a second meter and can be interrupted by
the power company at peak times.
• Remove the jumpers (dashed lines,
3
).
• Connect the permanent power supply to the controller
mains feed (
2
).
• Connect the low tariff power supply to the low tariff
mains feed (
1
).
• Connect the ripple control signal relay to terminal 13,
"EVU" (see Fig 6.7), if required by the power compa-
ny. The heat pump is blocked with this signal when the
contact is closed.
You will find an overview of the complete wiring dia-
gram in the appendix.
Electrical installation 6