1 Safety
4
Installation and maintenance instructions ecoTEC plus 0020261188_00
▶
If possible, close the gas isolator cock on
the product.
▶
Warn other occupants in the building by
yelling or banging on doors or walls.
▶
Leave the building immediately and ensure
that others do not enter the building.
▶
Alert the police and fire brigade as soon as
you are outside the building.
▶
Use a telephone outside the building to
inform the emergency service department
of the gas supply company.
1.3.3 Risk of death from leaks if the
product is installed below ground
level
Liquid gas accumulates at floor level. If the
product is installed below ground level, liquid
gas may accumulate at floor level if there
are any leaks. In this case, there is a risk of
explosion.
▶
Make sure that liquid gas cannot escape
from the product or the gas line under any
circumstance.
1.3.4 Risk of death due to blocked or
leaking flue gas routes
Installation errors, damage, tampering, unau-
thorised installation sites or similar can cause
flue gas to escape and result in a risk of pois-
oning.
What to do if you smell flue gas in the prop-
erty:
▶
Open all accessible doors and windows
fully to provide ventilation.
▶
Switch off the product.
▶
Check the flue gas routes in the product
and the flue gas diversions.
1.3.5 Risk of death due to explosive and
flammable materials
▶
Do not use the product in storage rooms
that contain explosive or flammable sub-
stances (such as petrol, paper or paint).
1.3.6 Risk of death due to lack of safety
devices
The schematic drawings included in this doc-
ument do not show all safety devices re-
quired for correct installation.
▶
Install the necessary safety devices in the
system.
▶
Observe the applicable national and inter-
national laws, standards and guidelines.
1.3.7 Risk of death from electric shock
There is a risk of death from electric shock if
you touch live components.
Before commencing work on the product:
▶
Unplug the mains plug.
▶
Or disconnect the product from the power
supply by switching off all power supplies
(electrical partition with a contact gap of at
least 3 mm, e.g. fuse or circuit breaker).
▶
Secure against being switched back on
again.
▶
Wait for at least 3 minutes until the capa-
citors have discharged.
▶
Check that there is no voltage.
1.3.8 Risk of death from escaping flue
gas
If you operate the product with an empty con-
densate siphon, flue gas may escape into the
room air.
▶
In order to operate the product, ensure that
the condensate siphon is always full.
Conditions
: Permitted B23 or B23P unit
types with condensate siphon (third-party
accessory)
–
Water seal level:
≥
200 mm
1.3.9 Risk of death due to cabinet-type
casing
Cabinet-type casing can give rise to danger-
ous situations when used on a product which
is operated with an open flue.
▶
Ensure that the product is supplied with
sufficient combustion air.
1.3.10 Risk of poisoning caused by
insufficient supply of combustion
air
Conditions
: Open-flued operation
▶
Ensure that the air supply to the product's
installation room is permanently unobstruc-
ted and sufficient in accordance with the
relevant ventilation requirements.