25
Installation and maintenance instructions auroSTEP plus 0020077748_FT1
• Release the screws (
2
) and remove the flange cover
(
1
).
Cleaning the tank
a
Caution!
Risk of corrosion if the inner tank is damaged.
Make sure the enamelling of the heat exchanger
and inner tank is not damaged during the
cleaning work.
• Clean the interior of the tank with a water jet. If nec-
essary, remove any deposits with an appropriate tool
(e. g. wooden or plastic scraper) and flush out the
deposits.
h
Note!
You must replace any old or damaged seals.
Fitting the flange cover
• Place the flange cover with its associated gaskets
back on the cleaning eye of the cylinder.
• Tighten the screws.
h
Note!
Check the magnesium protection anode too
each time before you refill the cylinder after
cleaning.
8.2
Servicing the magnesium protection anode
The cylinders are equipped with a magnesium protec-
tion anode which has to be checked the first time after
two years and then regularly once a year. A chain anode
is also available as a replacement part for the VIN SN
350 i.
Visual inspection
1
Fig. 8.2 Taking out the protection anode
• Take out the magnesium protection anode (
1
) each
time the cylinder is cleaned and check it for erosion.
• If necessary, exchange the magnesium protection
anode for an equivalent original replacement part.
h
Note!
You must replace any old or damaged seals.
• Tighten the protection anode firmly again after the
inspection.
• Fill the solar cylinder and check it for water leaks.
h
Note!
As an alternative to regular maintenance, we
recommend the installation of a maintenance-
free universal external current anode
(Part No. 302042, not available in all
countries).