150 Show Clock Param
Default = 0 (No)
Range: n/a
Level: 2
This parameter hides or reveals the Time of Day clock parameters (parameters
Enabling clock parameters also makes the Keeper parameters visible (see
).
The following data values may be assigned to this parameter:
Value
Description
0
No
1
Yes
151 Time Zone Setup
Default = 12 (-5 East. US)
Range: n/a
Level: 2 (Clock), Macro
This parameter allows configuration of clocks to account for time zones, in relation to Greenwich Mean
Time (GMT).
The following data values may be assigned to this parameter:
Value
Description
Value
Description Value Description
0
-12 Kwaj.
14
-4 Atlantic
28 +4 Baku
1
-11 Samoa
15
-4 Caracas 29 +5 Islambd
2
-10 Hawaii
16
-3 Brasilia 30 +6 Dhaka
3
-9 Alaska
17
-3 Greenland 31 +7 Bangkok
4
-8 Pac. US
18
-2 Mid Atl 32 +8 Beijing
5
-7 Mountain
19
-1 Azores 33 +9 Tokyo
6
-7 Chih.
20
0 London 34 +10 Sydney
7
-7 Arizona
21
0 Casablanca 35 +10 Vladiv.
8
-6 Cent. US
22
+1 C. Europe 36 +10 Guam
9
-6 Sask.
23
+1 C. Africa 37 +11 Magadan
10
-6 Mexico
24
+2 E. Europe 38 +12 Fiji
11
-6 Cent. Am
25
+2 Cairo 39 +12 N. Zeal.
12
-5 East. US
26
+3 Moscow 40 +13 Tonga
13
-5 Indiana
27
+3 Nairobi
152 TOD Run Enable
12:00
Range: 00:00 - 23:59
Level: 2 (Clock)
This parameter sets the starting time that the drive is enabled to run if a Run signal is active. If equal to
“Time Run Enable,” the function is disabled. (See
“Enabling the Vacon 500x Based on Time of Day (TOD)” on
154 TOD Run Disable
12:00
Range: 00:00 - 23:59
Level: 2 (Clock)
This parameter sets the ending time that the drive is enabled to run if a Run signal is active. If equal to
“Time Run Disable,” the function is disabled. (See
“Enabling the Vacon 500x Based on Time of Day (TOD)” on
156 TOD Run En 2
12:00
Range: 00:00 - 23:59
Level: 2 (Clock)
This parameter sets the starting time that the drive is enabled to run if a Run signal is active. If equal to
“Time Run Enable,” the function is disabled. (See
“Enabling the Vacon 500x Based on Time of Day (TOD)” on
158 TOD Run Dis 2
12:00
Range: 00:00 - 23:59
Level: 2 (Clock)
This parameter sets the ending time that the drive is enabled to run if a Run signal is active. If equal to
“Time Run Disable,” the function is disabled. (See
“Enabling the Vacon 500x Based on Time of Day (TOD)” on
160 Weekend TOD Enable
12:00
Range: 00:00 - 23:59
Level: 2 (Clock)
This parameter sets the starting time that the drive is enabled to run if a Run signal is active. If equal to
“Time Run Enable,” the function is disabled. (See
“Enabling the Vacon 500x Based on Time of Day (TOD)” on
162 Weekend TOD Dis
12:00
Range: 00:00 - 23:59
Level: 2 (Clock)
This parameter sets the ending time that the drive is enabled to run if a Run signal is active. If equal to
“Time Run Disable,” the function is disabled. (See
Содержание 500X
Страница 1: ...vacon 500x ac drives user s manual ...
Страница 9: ...24 hour support 358 0 40 837 1150 Email vacon vacon com summary of vacon 500x parameters vacon z 8 ...
Страница 13: ...24 hour support 358 0 40 837 1150 Email vacon vacon com introduction vacon z 12 1 ...
Страница 27: ...24 hour support 358 0 40 837 1150 Email vacon vacon com receiving and installation vacon z 26 3 ...
Страница 117: ...24 hour support 358 0 40 837 1150 Email vacon vacon com troubleshooting vacon z 116 8 ...
Страница 119: ...24 hour support 358 0 40 837 1150 Email vacon vacon com vacon 500x ultraflex options vacon 9 ...
Страница 121: ...24 hour support 358 0 40 837 1150 Email vacon vacon com appendix binary hexadecimal conversion vacon z 120 A ...
Страница 123: ......