204 Ref Select
Default = Vin1
Range: n/a
Level: 2
Parameter
204
, the Ref Select parameter, configures how the reference is determined when the reference
source is configured to terminals.
The following data values may be assigned to this parameter:
Parameter Value
Description
Vin1
Vin1 terminal (configured b
Cin
Cin terminal (configured b
Vin2
Vin2 terminal (configured by
Vin1 6FS
Vin1 terminal with 6x pulse train from a Vacon 500x, WFC, WF2 drive
Vin1 48FS
Vin1 terminal with 48x pulse train from a Vacon 500x, WFC, WF2 drive
Vin1+Cin
Sum of signal at Vin1 and the signal at Cin
Vin1+Vin2
Sum of signal at Vin1 and the signal at Vin2
Vin1-Cin
Difference between the signal at Vin and the signal at Cin
Vin1-Vin2
Difference between the signal at Vin and the signal at Vin2
Max Input
{2}
Greatest signal between Vin, Vin2 and Cin
Vin1/Cin DI
{1}
Switch between Vin and Cin using a Digital Input
Vin1/2 DI
{1}
Switch between Vin and Vin2 using a Digital Input
Vin1/KYP DI
{1}
Switch between Vin and Keypad reference using Digital Input
Cin/KYP DI
{1}
Switch between Cin and Keypad reference using Digital Input
Notes:
1.
The parameter that sets the function of the designated digital input must be configured as “Ref Switch” to complete the
implementation.
2.
The “Max Input” option will compare the inputs of all three analog inputs (Vin1, Vin2, Cin) and take the analog input with the highest
percentage input after span, offset, and inversion is applied.
205 Vin1 Config
Default = 0-10V
Range: n/a
Level: 2
Parameter
205, Vin1 Config,
selects the type of signal for analog input Vin1. Vin1 can be voltage, current,
or pulse train input. This parameter also determines input range, impedance, and characteristics.
Use
206 (Vin1 Offset)
and
to customize the selected range. The following data
values may be assigned to this parameter:
Parameter Value
Description
0-10V
0-10Vdc signal. This is the selection that is recommended when the drive is following
the 6FS or 48FS output of another drive.
0-10V Brk W
0-10Vdc signal with broken wire detection for speed pot operation
0-10V I
0-10Vdc signal Inverted
0-10V Bipol
0-10Vdc signal
(5Vdc is stop with 0Vdc Full Rev and 10Vdc Full FWD)
0-5V
0-5Vdc signal
0-5V I
0-5Vdc signal Inverted
0-20mA 250
0 to 20 mA current signal with 250 Ohm load
0-20mA 250I
0 to 20 mA current signal with 250 Ohm load Inverted
4-20mA 250
4 to 20 mA current signal with 250 Ohn load load
4-20mA 250I
4 to 20 mA current signal with 250 Ohm load Inverted
PT 0-1kHz
0 to 1 kHz pulse train
PT 0-10kHz
0 to 10 kHz pulse train
PT 0-100kHz
0 to 100 kHz pulse train
When the signal range is inverted (that is, the minimum input corresponds to the maximum output, while the
maximum input corresponds to the minimum output).
206 Vin1 Offset
Default = 0.00%
Range: 0.0 to 100.0%
Level: 2
Parameter
206, Vin1 Offset, configures the input range (offset) for analog input Vin1 that will affect speed
or torque limit functions. It is expressed as a percentage of the maximum value of the input signal.
Note that if the input signal drops below the offset value or if the input signal is lost (if no offset is
configured), fault 22 will be generated.
207 Vin1 Span
Default = 100%
Range: 10.0 to 200.0%
Level: 2
Parameter
207,
the Vin1 Span parameter, is used to alter the input range (span) of the input signal for
analog input Vin1
that will affect speed or torque limit functions
. For example, if
205, Vin1
Config,
selects the 0 to 10 Vdc input signal, setting this parameter to 50% reduces it to 0 to 5 Vdc.
208 Cin Config
Default = 0-20mA 50
Range: n/a
Level 2
Содержание 500X
Страница 1: ...vacon 500x ac drives user s manual ...
Страница 9: ...24 hour support 358 0 40 837 1150 Email vacon vacon com summary of vacon 500x parameters vacon z 8 ...
Страница 13: ...24 hour support 358 0 40 837 1150 Email vacon vacon com introduction vacon z 12 1 ...
Страница 27: ...24 hour support 358 0 40 837 1150 Email vacon vacon com receiving and installation vacon z 26 3 ...
Страница 117: ...24 hour support 358 0 40 837 1150 Email vacon vacon com troubleshooting vacon z 116 8 ...
Страница 119: ...24 hour support 358 0 40 837 1150 Email vacon vacon com vacon 500x ultraflex options vacon 9 ...
Страница 121: ...24 hour support 358 0 40 837 1150 Email vacon vacon com appendix binary hexadecimal conversion vacon z 120 A ...
Страница 123: ......