Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
41
z
vacon operation and programming
5
Program mode is entered by stopping the drive and pressing the Program (PROG) key for Level 1 access;
or holding down SHIFT while pressing PROG for Level 2 access. Pressing and holding the Enter key and
then pressing the Program key will show only those parameters that have been changed from the factory
defaults. Table 2 describes the function of the keys in Program mode.
Press this key to have the drive enter Program mode and have Level 1 parameters available.
(To access Level 2 parameters, hold down SHIFT while pressing this key; to access Macro
mode, hold down the PROG key for more than 3 seconds.) Once Program mode is active,
pressing this key at any time returns the drive to the Operation mode. If an Access Code has
been programmed, it must be entered to proceed with programming. See
811
(Access Code)
NOTE: To see what parameters have changed from the factory default, press ENTER + PROG.
If the display flashes “Factory Defaults,” no parameters have changed.
In the Program mode, pressing this key scrolls forward through the parameters. If the P
indicator is flashing, it increases the value of the parameter. To change the scroll rate, hold
the SHIFT key at the same time to increase the scroll rate; release the SHIFT key to return
to the normal scroll rate. Press the ENTER key to store the new value.
In the Program mode, pressing this key scrolls backward through the parameters. If the P
indicator is flashing, it decreases the value of the parameter. To change the scroll rate, hold
the SHIFT key at the same time to increase the scroll rate; release the SHIFT key to return
to the normal scroll rate. Press the ENTER key to store the new value.
NOTE: If the P indicator on the keypad display is flashing, momentarily pressing and
releasing both the UP and DOWN arrows at the same time restores the parameter to the
factory default value. Press ENTER to store the new value.
Pressing this key while a parameter is displayed allows that parameter to have its value
changed by use of the UP and DOWN arrow keys. The P indicator flashes to show that the
parameter can be programmed. See also the descriptions for the UP and DOWN arrows
above to see how they work with the SHIFT key.
This key must be pressed after the value of a parameter has been changed to store the new
value. The display will show “stored” for one second indicating that the new value has been
entered into memory.
NOTE: The Vacon 500x unit allows you to view only those parameters that have changed. If you
press keypad keys ENTER and PROGram simultaneously, only those parameters that have
been changed from the factory defaults will be shown.
Table 2: Function of Keys in Program Mode
Содержание 500X
Страница 1: ...vacon 500x ac drives user s manual ...
Страница 9: ...24 hour support 358 0 40 837 1150 Email vacon vacon com summary of vacon 500x parameters vacon z 8 ...
Страница 13: ...24 hour support 358 0 40 837 1150 Email vacon vacon com introduction vacon z 12 1 ...
Страница 27: ...24 hour support 358 0 40 837 1150 Email vacon vacon com receiving and installation vacon z 26 3 ...
Страница 117: ...24 hour support 358 0 40 837 1150 Email vacon vacon com troubleshooting vacon z 116 8 ...
Страница 119: ...24 hour support 358 0 40 837 1150 Email vacon vacon com vacon 500x ultraflex options vacon 9 ...
Страница 121: ...24 hour support 358 0 40 837 1150 Email vacon vacon com appendix binary hexadecimal conversion vacon z 120 A ...
Страница 123: ......