Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
61
z
vacon
vacon 500x parameters
7
7. VACON 500X PARAMETERS
7.1 Introduction
The Vacon 500x AC drive incorporates a comprehensive set of parameters that allow you to configure the
device to meet the special requirements of your particular application.
Note that pressing the PROG key enters Level 1 programming. Press SHIFT+PROG to enter Level 2
programming. Press ENTER+PROG to show only those parameters that have changed from the factory
default values.
This chapter describes the available parameters and the values that may be assigned to them. The
parameter summary table at the front of this manual provides a summary of all parameters including their
ranges and default values.
7.2 Level 1 Parameters
The most commonly configured Vacon 500x parameters are stored in a group named Level 1. This group is
easily accessed by pressing the PROG key as described in Chapter 5: “Operation and Programming” on
page 39. The following table lists the parameters in this group; for further information on the parameter,
please turn to the indicated page.
.
7.3 Description of Parameters
Table 2 lists the Vacon 500x parameters in the order in which they appear in the keypad display. For each
parameter, the table lists the default value and range and also describes the use of the parameter.
Para. #
Parameter Name
See
Page
Para. #
Parameter Name
See
Page
001
Model Number
303
Preset Freq 1
102
Output Freq
402
Accel Time 1
103
Output Voltage
403
Decel Time 1
104
Output Current
502
Voltage Boost
105
Drive Load
610
Timed OL Select
106
Load Torque
700
Vmet Config
107
Drive Temp
705
Relay 1 Select
111
DC Bus Voltage
706
Relay 2 Select
201
Input Mode
202
Rev Enable
301
Min Frequency
302
Max Frequency
Table 1: Parameters Available in Level 1 Programming (Factory Macro)
001 Model Number
Read-Only
Range: n/a
Level: 1,2
Parameter
001
, the Model Number parameter, contains the portion of the Vacon 500x model number
related
to voltage and horsepower. The number format is
vvhhf, where vv is the code for the input voltage (20=230
Vac, three-phase; 40=460 Vac, three-phase; 50=575 Vac, three-phase);
hh is horsepower; and
f is the
fractional part the horsepower. Example: 20050 = 230 Vac, three-phase, 4.0 kW/5.0 HP model.
002 Software Rev
Read-Only
Range: 0.00-99.99
Level: 2
Parameter
002,
the Software Revision parameter, displays the software revision that is installed in the
drive.
Options: 0.00-99.99
Содержание 500X
Страница 1: ...vacon 500x ac drives user s manual ...
Страница 9: ...24 hour support 358 0 40 837 1150 Email vacon vacon com summary of vacon 500x parameters vacon z 8 ...
Страница 13: ...24 hour support 358 0 40 837 1150 Email vacon vacon com introduction vacon z 12 1 ...
Страница 27: ...24 hour support 358 0 40 837 1150 Email vacon vacon com receiving and installation vacon z 26 3 ...
Страница 117: ...24 hour support 358 0 40 837 1150 Email vacon vacon com troubleshooting vacon z 116 8 ...
Страница 119: ...24 hour support 358 0 40 837 1150 Email vacon vacon com vacon 500x ultraflex options vacon 9 ...
Страница 121: ...24 hour support 358 0 40 837 1150 Email vacon vacon com appendix binary hexadecimal conversion vacon z 120 A ...
Страница 123: ......