vacon 500x parameters
7
705 Relay 1 Select
706 Relay 2 Select
707 DO1 Select
708 DO2 Select
Default: Drv Fault
Default: Drv Run
Default: Drv Ready
Default: At Speed
Range for Parameters 705-708: n/a
Levels 1, 2 for Parameters 705-706
Level 2 for Parameters 707-708
These four parameters configure what condition will cause relays R1, R2, DO1, and DO2 to activate.
Parameter 705 is associated with relay R1; parameter 706 with relay R2; parameter 707 with DO1; and
parameter 708 with relay DO2. The following values may be assigned:
Parameter Value
Description
Drv ReadyThe drive is ready. (The relay will be open in Fault and Low Voltage conditions.)
608 (Restart Number)
.)
Drive RunThe drive has received a direction command.
Running FWDThe motor is running Forward and the output frequency is above 0.5 Hz.
Running REVThe motor is running in Reverse and the output frequency is above 0.5 Hz.
Zero SpeedThe drive is in Run mode, but the speed reference is 0 Hz.
At SpeedThe drive has reached reference speed.
Current LimCurrent Limit mode is active.
High TempThe temperature limit of the drive has been exceeded.
Local ModeThe keypad is the control path for reference speed and control functions.
SeqOut-000Programmed sequence step active. SeqOut-
XXX values are all status
SeqOut-001outputs linked to a step in the program sequencer.
SeqOut-010
SeqOut-011See
“Using the Vacon 500x Program Sequencer” on page 98
for more information.
SeqOut-100
SeqOut-101
SeqOut-110
SeqOut-111
Thres 1Active status of Threshold 1 for this output (see parameter 740 on page 85)
Thres 2Active status of Threshold 2 for this output (see parameter 743 on page 85)
Timer 1Active status of Timer 1 for this output (see parameter 746 on page 86)
Timer 2Active status of Timer 2 for this output (see parameter 749 on page 86)
ARCTICWhen a digital output is configured to use this option, the output will be active when the Arctic Mode is turning
on the DB resistor. This option will turn on when the temperature drops below the Arctic mode entry point, which is -
7°C. This will work even if Arctic Mode is not enabled.
DI-FWD
DI-REVDI-xxx values all refer to inputs on option cards;
DI-R/Jwhen the respective input is active, the respective
DI-ENoutput listed here is set.
DI-MOL
DI1
DI2 DI-x values all refer to inputs on the drive control board;
DI3 when the respective input is active, the respective
DI4 output listed here is set.
DI5
Reminder 1User-defined reminder
Reminder 2User-defined reminder
Reminder 3User-defined reminder
SIO ConfigIndicates the setting that the output will respond to, set in parameters 921 (SIO Imet Lvl) and 907
(Control Word)
TOD InhibitIndicates the drive is disabled based on the time set in TOD run enable parameters.
720 Active Logic
Default: Active High
Range: n/a
Level 2
Содержание 500X
Страница 1: ...vacon 500x ac drives user s manual ...
Страница 9: ...24 hour support 358 0 40 837 1150 Email vacon vacon com summary of vacon 500x parameters vacon z 8 ...
Страница 13: ...24 hour support 358 0 40 837 1150 Email vacon vacon com introduction vacon z 12 1 ...
Страница 27: ...24 hour support 358 0 40 837 1150 Email vacon vacon com receiving and installation vacon z 26 3 ...
Страница 117: ...24 hour support 358 0 40 837 1150 Email vacon vacon com troubleshooting vacon z 116 8 ...
Страница 119: ...24 hour support 358 0 40 837 1150 Email vacon vacon com vacon 500x ultraflex options vacon 9 ...
Страница 121: ...24 hour support 358 0 40 837 1150 Email vacon vacon com appendix binary hexadecimal conversion vacon z 120 A ...
Страница 123: ......