vacon 500x parameters
vacon
z
102
7
Vacon 500x Sequencer Ramping Selection
When the sequencer is active, the active ramp is no longer determined by parameter “Ramp Select.” The
user, however, does have the choice of using the main ramps (Accel Time 1/Decel Time1), or the alternate
ramp sets (Accel Time 2/Decel Time 2...3, 4) for each independent state. This is determined by bits 4 and 5
of the step’s control parameter. The following chart shows the selection of ramp times based on how bits
4 and 5 are set for the control parameter:
Sequencer Output Configuration
The Vacon 500x Program Sequencer allows digital outputs to be activated during states of the sequencer.
This function could be used to activate other devices in a system or to signal to an operator when a part of
the sequence is active. The user sets the digital output by setting bits 13-15 of the control parameter with
a binary value, and then sets a digital output parameter with the option for that same binary value. For
example, if a control state was output configured for a binary value of 111, then any digital output
configured to “SeqOut-111” would be activated during that time. The following chart shows the output
configuration options for the Vacon 500x drive:
Vacon 500x Sequencer Control Selection
The Vacon 500x Program Sequencer allows several control selection options not available in the X4
Program Sequencer. These new options allow a terminal strip control state, or a state that faults the drive.
1100
Value of parameter Preset Freq 12 (315)
1101
Value of parameter Preset Freq 13 (316)
1110
Value of parameter Preset Freq 14 (317)
1111
Value of parameter Preset Freq 15 (318)
Binary
Value
Definition (Resultant Speed)
00
Accel Time 1 and Decel Time 1 will be the ramp times for this step.
01
Accel Time 2 and Decel Time 2 will be the ramp times for this step.
10
Accel Time 3 and Decel Time 3 will be the ramp times for this step.
11
Accel Time 4 and Decel Time 4 will be the ramp times for this step.
Table 5: Ramp Selection Options
Binary Value
Definition (Output Configuration)
000
Any digital output (or relay output) configured for SeqOut-000 is active in this state.
001
Any digital output (or relay output) configured for SeqOut-001 is active in this state.
010
Any digital output (or relay output) configured for SeqOut-010 is active in this state.
011
Any digital output (or relay output) configured for SeqOut-011 is active in this state.
100
Any digital output (or relay output) configured for SeqOut-100 is active in this state.
101
Any digital output (or relay output) configured for SeqOut-101 is active in this state.
110
Any digital output (or relay output) configured for SeqOut-110 is active in this state.
111
Any digital output (or relay output) configured for SeqOut-111 is active in this state.
Table 6: Output Selection Options
Binary
Value
Definition (Resultant Speed)
Table 4: Speed Selection Options
Содержание 500X
Страница 1: ...vacon 500x ac drives user s manual ...
Страница 9: ...24 hour support 358 0 40 837 1150 Email vacon vacon com summary of vacon 500x parameters vacon z 8 ...
Страница 13: ...24 hour support 358 0 40 837 1150 Email vacon vacon com introduction vacon z 12 1 ...
Страница 27: ...24 hour support 358 0 40 837 1150 Email vacon vacon com receiving and installation vacon z 26 3 ...
Страница 117: ...24 hour support 358 0 40 837 1150 Email vacon vacon com troubleshooting vacon z 116 8 ...
Страница 119: ...24 hour support 358 0 40 837 1150 Email vacon vacon com vacon 500x ultraflex options vacon 9 ...
Страница 121: ...24 hour support 358 0 40 837 1150 Email vacon vacon com appendix binary hexadecimal conversion vacon z 120 A ...
Страница 123: ......