7
416 Decel Time 3
Default: 10.0 s
Range: 0.1 to 3200.0 s
Level 2
to 0 Hz. This deceleration ramp is
401 (Ramp Select)
or Sequencer Configuration.
Note that extremely short deceleration times may result in nuisance fault trips or may require an external
dynamic brake or regen current limit.
417 Accel Time 4
Default: 15.0 s
Range: 0.1 to 3200.0 s
Level 2
302 (Max Frequency)
401 (Ramp Select)
or Sequencer Configuration.
Note that extremely short acceleration times may result in nuisance fault trips.
418 Decel Time 4
Default: 15.0 s
Range: 0.1 to 3200.0 s
Level 2
to 0 Hz. This deceleration ramp is
401 (Ramp Select)
or Sequencer Configuration.
Note that extremely short deceleration times may result in nuisance fault trips or may require an external
dynamic brake or regen current limit.
490 Appl Macro
Default: 0 (Factory)
Range: n/a
Macro
This parameter configures what macro will be active in the drive. A macro will change a default or the
visibility of a parameter.
Parameter Value
Description
0
Factory
1
Fan
2
Fan w/ PID
3
Pump
4
Pump w/ PID
5
Vector
491 Seq Appl
Default: 0 (Disabled)
Range: n/a
Macro
This parameter configures whether sequencer parameters are visible, and it also defines the time base of
the sequencer. The time base may change depending on the drive’s timing loops.
Parameter Value
Description
0
Disabled
1
1 sec base
2
.1 sec base
3
.01 sec base
492 SIO Visible
Default: 0 (No)
Range: n/a
Macro
This parameter configures whether SIO parameters are visible.
Options are 0 (No) and 1 (Yes).
The following parameters are made visible if this option is set to Yes:
SIO Protocol (900)Status Word (908)FBus Write 3 (892)
SIO Baudrate (901)FBus Read 1 (880)FBus Write 4 (893)
Comm Drop # (902)FBus Read 2 (881)FBus Write 5 (894)
Infrared Baud (916)FBus Read 3 (882)SIO Vmet Level (920)
SIO Timer (903)FBus Read 4 (883)SIO Imet Level (921)
SIO Cntl Word (904)FBus Read 5 (884)Status Word 2 (926)
Ext Ref Freq 1 (905)FBus Write 1 (890)Cntl Word 2 (907)
Ext Ref Freq 2 (906)FBus Write 2 (891)FBus Port Config (917)
Содержание 500X
Страница 1: ...vacon 500x ac drives user s manual ...
Страница 9: ...24 hour support 358 0 40 837 1150 Email vacon vacon com summary of vacon 500x parameters vacon z 8 ...
Страница 13: ...24 hour support 358 0 40 837 1150 Email vacon vacon com introduction vacon z 12 1 ...
Страница 27: ...24 hour support 358 0 40 837 1150 Email vacon vacon com receiving and installation vacon z 26 3 ...
Страница 117: ...24 hour support 358 0 40 837 1150 Email vacon vacon com troubleshooting vacon z 116 8 ...
Страница 119: ...24 hour support 358 0 40 837 1150 Email vacon vacon com vacon 500x ultraflex options vacon 9 ...
Страница 121: ...24 hour support 358 0 40 837 1150 Email vacon vacon com appendix binary hexadecimal conversion vacon z 120 A ...
Страница 123: ......