vacon 500x parameters
vacon
z
70
7
309 Cut-Off Freq
Default: 0.0 Hz
Range: 0.0 to 5.0 Hz
Level 2
This parameter sets the point where the drive no longer attempts to spin the motor. The range of this
parameter is 0.0-5.0 Hz. When the parameter is configured to a value of 0.0 Hz, the drive will operate with
no Cut-off Frequency. If the function is enabled, the drive will be able to ramp up through the cut-off
frequency range, as in normal operation. If the speed command falls below the cut-off frequency, the drive
stops “gating” the outputs and coasts down to zero speed. The keypad display will indicate Zero Speed, and
the Forward or Reverse LED will be lit depending on the command. When the reference returns to a value
greater than the cut-off frequency, the drive will ramp from 0.0 Hz to the reference frequency.
380 Keeper Input Cfg
Default: Disabled
Range: n/a
Level 2 (Clock)
This parameter allows you to enable and configure a data logger feature called the “Keeper.” The Keeper
parameters
are hidden until you enable the Clock parameters (select Yes for parameter
150, Show Clock Parameters). The following parameter values determine the input for the Keeper:
Parameter Value
Description
0
Disabled
1
Vin1
2
Cin
3
Vin2
4
Encoder
For detailed information about setting up Keeper parameters, see
“Using the Keeper Data Log” on page 49
.
381 Keeper Max Scale
Default: 1000
Range: 1 - 32000
(units dependent on parameter 389)
Level 2 (Clock)
This parameter configures the value of the Keeper input signal when the analog input is at its maximum
value. For detailed information about setting up Keeper parameters, see
“Using the Keeper Data Log” on
382 Keeper Save Time
Default: 0:00
Range: 00:00 - 23:59
Level 2 (Clock)
This parameter sets the time of each day when the Keeper will save an accumulated process variable. For
detailed information about setting up Keeper parameters, see
“Using the Keeper Data Log” on page 49
.
384 Keeper Save Rate
Default: 24 hour
Range: n/a
Level 2 (Clock)
This parameter configures whether the Keeper will collect multiple records during a day, with these
options:
Parameter Value
Description
0
24 Hour
1
12 Hour
2
8 Hour
For detailed information about setting up Keeper parameters, see
“Using the Keeper Data Log” on page 49
.
385 Keeper Input Value
Default: Read-only
Range: 0 - 32000
Levels 2 (Clock)
This parameter provides feedback to display the current value of the Keeper input. For detailed information
about setting up Keeper parameters, see
“Using the Keeper Data Log” on page 49
386 Keeper Time Rate
Default: 1 (Minute)
Range: n/a
Level 2 (Clock)
This parameter configures the tiime base of the Keeper accumulation. The setting of this variable is
dependent on the process variable.
The following parameter values are valid:
Parameter Value
Description
0
Second
1
Minute
2
Hour
For detailed information about setting up Keeper parameters, see
“Using the Keeper Data Log” on page 49
.
387 Keeper Rec. Num
Default: Read-only
Range: 0 - 128
Levels 2 (Clock)
This parameter shows how many records have been saved by the Keeper. For detailed information about
setting up Keeper parameters, see
“Using the Keeper Data Log” on page 49
.
Содержание 500X
Страница 1: ...vacon 500x ac drives user s manual ...
Страница 9: ...24 hour support 358 0 40 837 1150 Email vacon vacon com summary of vacon 500x parameters vacon z 8 ...
Страница 13: ...24 hour support 358 0 40 837 1150 Email vacon vacon com introduction vacon z 12 1 ...
Страница 27: ...24 hour support 358 0 40 837 1150 Email vacon vacon com receiving and installation vacon z 26 3 ...
Страница 117: ...24 hour support 358 0 40 837 1150 Email vacon vacon com troubleshooting vacon z 116 8 ...
Страница 119: ...24 hour support 358 0 40 837 1150 Email vacon vacon com vacon 500x ultraflex options vacon 9 ...
Страница 121: ...24 hour support 358 0 40 837 1150 Email vacon vacon com appendix binary hexadecimal conversion vacon z 120 A ...
Страница 123: ......