Chapter 3: Configuration and commissioning
48
ZP1-X3E Series Installation Manual
The available settings for this feature are shown below.
Display
Description
Manual-automatic and manual-only mode.
With this setting, the key functionality is as follows:
•
If the key is turned to ON, the panel is set to Manual
mode
•
If the key is turned to OFF, the panel is set to
Automatic mode
Access level functionality (default).
With this setting, the key functionality is as follows:
•
If the key is turned to ON, operator level is active
•
If the key is turned to OFF, public level is active
Note
If the manual key mode setting is On, the key takes priority over the keypad and
network related commands:
• If the key position is On (that is, the key is inserted and turned) the panel will
stay in manual mode independently of the operator level auto/manual button
actions on the keypad and related network commands.
• If the key position is OFF (that is, the key is not inserted or is inserted but not
turned) the panel accepts an operator level request to change the
auto/manual using the button or the related network commands.
Enable flooding time
Use this menu to enable the control of the flooding time. The flooding time is the
time that the actuator remained activated (5 to 300 seconds in steps of 5
seconds). The default setting is off.
To enable the flooding time:
1. Set the display as shown below, and then press Enter.
The red Released LED flashes fast to indicate that the configuration menu is
active.
2. Select a value using the value selection buttons (2 and 4).
3. Press Enter
4. Save your changes.