Chapter 3: Configuration and commissioning
ZP1-X3E Series Installation Manual
35
To configure an actuator delay:
1. Set the display as shown below, and then press Enter.
The red Release LED flashes fast to indicate that the delay configuration
menu is active.
2. Select a delay value from 00 to 60 seconds using the value selection buttons
(2 and 4).
3. Press Enter.
4. Save your changes.
Reset disabled delay
When the control panel enters extinguishing activation, the reset disabled delay
starts counting down, and the reset is disabled until the delay expires.
Use this menu to configure a reset disabled delay of up to 30 minutes (in steps of
1 minute). The default setting is for a 2-minute delay.
To configure a reset disabled delay:
1. Set the display as shown below, and then press Enter.
2. Select a delay value from 00 to 30 minutes using the value selection buttons
(2 and 4).
3. Press Enter.
4. Save your changes.
Fire sounders delay
Use this menu to configure a fire sounders delay of up to 10 minutes. The default
setting is 00 (no delay). For more information on delay operation, see “Fire delay
operation” on page 36.
To configure a fire sounders delay:
1. Set the display as shown below, and then press Enter.
The Fire Sounders Delay LED flashes fast to indicate that the sounder delay
configuration menu is active.