Chapter 3: Configuration and commissioning
40
ZP1-X3E Series Installation Manual
Display
Menu
Values
Firenet initial zone number
0001 to 9999
Default: 0001
The number has four digits. Identified
by position, these are: 1234.
Press Up to enter the first two digits of
the number (positions 1 and 2).
Press Down to enter the last two digits
of the number (positions 3 and 4).
Firenet global controls
ON/OFF
Default: On
Firenet loop class
A/ B
Default: B
Process remote zones
ON/OFF
Default: On
Firenet map
01 to 32
ON/OFF
On for nodes 1 and 2, Off for the rest
Firenet repeater map
01 to 32
ON/OFF
On for nodes 1 and 2, Off for the rest
Firenet analogue repeater remote node
ON/OFF
Default: Off
Firenet remote output control
ON/OFF
Default: Off
Extinguishing Firenet global controls
ON/OFF
Default: Off
Software version
Read-only
Configuration version
Read-only
Configuration time stamp
Read-only
Configuration date stamp
Read-only
Zone configuration
Passive EOL
Active EOL
Passive EOL with CleanMe
Active EOL with CleanMe
Intrinsically safe
Zenner EOL
Unlatched (only for BS 7273 mode and
fire zones)