Chapter 2: Installation
14
ZP1-X3E Series Installation Manual
Connecting a remote reset device
The remote reset input allows the control panel to be reset from a remote
location. The reset operation is the same as using the Reset button on the
control panel user interface.
Note:
EU ordinances and regulations require the use of a key switch to control
access to this function.
The remote reset is executed when the input device switches from deactivated to
activated. See “Input and output specifications” on page 81 for the impedance
values for this unsupervised input.
Connecting outputs
Output functionality
Each control panel has eight outputs, marked OUT1 to OUT8 on the control
panel PCB. Output functionality is shown in Table 8 below.
Table 8: Output functionality
Output
Function
Type and status
OUT1
Hold extinguishing manual call point
Free-of-voltage (unsupervised switch)
Hold inactive = open
Hold active = closed
OUT2
Abort extinguishing manual call point
Disable extinguishing switch
(BS 7273 mode)
Free-of-voltage (unsupervised switch)
Abort inactive = open
Abort active = closed
Free-of-voltage (unsupervised switch)
Enabled = open
Disabled = closed
OUT3
Manual-only mode
Free-of-voltage (unsupervised switch)
Manual-automatic = open
Manual-only = closed
OUT4
Extinguishing released
Free-of-voltage (unsupervised switch)
Released inactive = open
Released = closed
OUT5
Fire sounders
Supervised (standard)
Off = −11 VDC (supervision)
On = +24 VDC
OUT6
Extinguishing sounders
Supervised (standard)
Off = −11 VDC (supervision)
On = +24 VDC
OUT7
Extinguishing released optical warning
panels or signs
Supervised (standard)
Off = −11 VDC (supervision)
On = +24 VDC