Chapter 3: Configuration and commissioning
46
ZP1-X3E Series Installation Manual
To configure the extinguishing zones:
1. Set the display as shown below, and then press Enter.
The Zone yellow LEDs flash quickly to indicate that the configuration menu is
active.
2. Select a value using the value selection buttons (2 and 4).
3. Press Enter.
4. Save your changes.
The available settings for this feature are shown below.
Display
Description
Z1 is configured as an extinguishing zone.
Z2 and Z3 are configured as fire detection zones.
Z1 and Z2 are configured as extinguishing zones.
Z3 is configured as a fire detection zone.
Z1, Z2, and Z3 are configured as extinguishing zones.
No fire detection zones are provided.
No extinguishing zones are provided. Z1, Z2, Z3 are
configured as fire detection zones.
Manual-only mode local
When the control panel is in manual-only mode, the extinguishing process can
only be initiated manually, using the MCP Start device. Automatic extinguishing
events reported from the fire detection zones are disabled for extinguishing
activation.
The panel can be switched to manual-only mode using two methods: by pressing
the Manual Mode button on the control panel interface (local activation), or by a
manual-only mode activation device, such as an external switch (remote input
activation). A remote command can be transmitted from the network.
Use this option to configure which method is used to switch to manual-only
mode. The default configuration is On (the Manual Mode button on the control
panel interface is used for local activation).
For more information see “Connecting an external device for manual-only mode
control” on page 12.