Chapter 3: Configuration and commissioning
ZP1-X3E Series Installation Manual
33
To change the operation mode configuration preset:
1. Set the display as shown below, and then press Enter.
2. Select a value using the value selection buttons (2 and 4).
3. Press Enter.
4. Save your changes.
Supervision mode
Use this menu to configure the supervision mode.
To configure the supervision mode:
1. Set the display as shown below, and then press Enter.
2. Select a value using the value selection buttons (2 and 4). The Zone LEDs
flashes fast to indicate that the supervision mode is active.
3. Press Enter.
4. Save your changes.
The available settings for this feature are shown below.
Display
Description
EN 54-13 supervision On for zone and class A
expansion board outputs.
Standard zone supervision with class B fire outputs
(default).
Note:
This menu is not visible if the panel operational mode is BS 7273 (either
stage 1 or stage 2) or includes CleanMe configuration. These options only allow
standard EN 54-2 zone supervision with class B outputs.
Panel mode
Use this read-only menu to view the operating mode of the control panel.
To view the panel mode:
1. Set the display as shown below, and then press Enter.