Chapter 3: Configuration and commissioning
44
ZP1-X3E Series Installation Manual
The available settings for this feature are shown below.
Display
Description
Mode A: The actuator delay countdown continues during
MCP Hold activation.
Mode B: The actuator delay countdown restarts when
the MCP Hold device is restored. MCP Hold is indicated
using a specific sounder tone.
Activation tone
Use this menu to set the extinguishing activation tone of the extinguishing
sounders on the control panel PCB: continuous or pulsed. The pulsed pattern is
1 second on, 1 second off. The default setting is pulsed mode.
To configure the activation tone:
1. Set the display as shown below, and then press Enter.
The red Extinguishing Sounders LED flashes fast to indicate that the
configuration menu is active.
2. Select a value using the value selection buttons (2 and 4).
3. Press Enter.
4. Save your changes.
The available settings for this feature are shown below.
Display
Description
Pulsed mode
Continuous mode
Released tone
Use this menu to set the extinguishing released tone of the extinguishing
sounders on the control panel PCB: continuous or pulsed. The pulsed pattern is
1 second on, 1 second off. The default setting is continuous mode.