Chapter 3: Configuration and commissioning
34
ZP1-X3E Series Installation Manual
Display indications for each operating mode are shown below.
Display
Panel mode
Description
Basic standard
Fire sounders cannot be manually activated (fire
sounders are only activated if there is a fire alarm).
Basic evacuation
Fire sounders can be manually activated at operator
user level (a fire alarm is not required).
BS 7273 mode stage 1
Fire sounders cannot be silenced automatically after
the panel changes from pre-activated to activated
state. They cannot be silenced automatically after the
panel changes from ‘Activated’ to ‘Released’ state.
BS 7273 mode stage 2
Fire sounders cannot be silenced automatically after
the panel changes from pre-activated to activated
state. They cannot be silenced automatically after the
panel changes from ‘Activated’ to ‘Released’ state.
Repeater with fire routing
(EN 54-2)
Fire routing functionality can be repeated.
Repeater with fire routing
(BS 7273)
Fire routing functionality can be repeated.
Custom
A custom operating mode is configured. The display
alternates between CU (custom) and the operation
mode.
Note:
In basic evacuation operating mode, the configured actuator delay is
bypassed when MCP Start is activated. The actuator output is activated
immediately.
Custom panel operating mode
A custom panel operating mode will be indicated if any of the following zone
configuration settings are changed from the operating mode preset values:
• Zone delay
• Zone configuration
• Zone type
Actuator delay
When the control panel enters the extinguishing activation state, the actuator
delay starts counting down. The extinguishing actuator output is activated when
the delay time expires. (Activation of the MCP Hold or MCP Abort point prevents
the panel from entering the extinguishing activation state.)
Use this menu to configure an actuator delay of up to 60 seconds (in steps of 5
seconds). The default setting is for a 10-second delay.