• Uponor AquaPEX piping shall not be installed in locations with
direct exposure to sunlight.
• Piping shall be supported every 24" with metal pipe hangers
designed for use with non-metallic pipe/
piping. Follow
minimum bend radius limitations as detailed on page 26 of
this installation guide. Drilling through joists is an acceptable
method of support if allowed by the AHJ, joist manufacturer,
and applicable building codes.
Exposed finished ceiling assemblies
• Ceiling shall be horizontal and must be finished with minimum
33
⁄
88
"-thickness gypsum wallboard, a suspended membrane
ceiling with lay-in panels or tiles having a minimum weight
of 0.35 lf/ft
2
installed with metallic support grids, or ½"-thick,
code-complying plywood or solid sheathing.
• Piping shall be supported every 24" with metal supports
designed for use with non-metallic pipe/piping. Follow
minimum bend radius limitations as detailed on page 26 of
this installation guide. Drilling through joists is an acceptable
method of support if allowed by the AHJ, joist manufacturer,
and applicable building codes.
• Listed residential sprinklers with an activation temperature of
155°F (68.3°C) and 4.9 minimum K-factor shall be used in the
exposed portion of the sprinkler system. Sprinkler spacing shall
be no larger than 16 ft. Per NFPA 13D, sprinklers shall be ins
talled
with deflectors no more than 1¾" below the bottom of the joist
to account for future finished ceilings.
uponor-usa.com
|
uponor.ca
l 3
Содержание AquaSAFE
Страница 1: ...Uponor AquaSAFE System Installation Guide...
Страница 36: ...30 l Uponor AquaSAFE System Installation Guide...
Страница 54: ...48 l Uponor AquaSAFE System Installation Guide...
Страница 56: ...50 l Uponor AquaSAFE System Installation Guide...
Страница 62: ...56 l Uponor AquaSAFE System Installation Guide...
Страница 68: ...62 l Uponor AquaSAFE System Installation Guide...
Страница 71: ...uponor usa com uponor ca l 65...