Figure 1-4: Concealed
sprinkler
Figure 1-5: Concealed
sprinkler cover plate
Figure 1-6: Recessed
pendent sprinkler
Figure 1-7:
Flat concealed
sidewall sprinkler
Concealed sprinklers
Concealed sprinklers feature a plate that
drops away from the sprinkler when the
temperature reaches between 135°F (57°C)
and 140°F (60°C). The sprinkler activates
when the temperature reaches between
162°F (72°C) and 165°F (74°C). In areas
where ambient ceiling temperatures
exceed 100°F (38°C), intermediate-
temperature sprinklers are required.
Caution: Do not paint cover plates.
Paint coverage may interfere with
the heat sensitivity of the sprinkler.
Recessed pendent sprinklers
Recessed pendent sprinklers are visible
in the ceiling and do not use a cover
plate. Recessed sprinklers activate when
temperatures exceed 155°F (68°C). In
areas where ambient ceiling temperatures
exceed 100°F (38°C), intermediate
temperature sprinklers are required.
Flat concealed horizontal
sidewall sprinklers
Flat concealed horizontal sidewall
sprinklers are installed in the wall and
concealed by a special flat cover plate
that releases prior to sprinkler operation
at 165°F (74°C).
uponor-usa.com
|
uponor.ca
l 11
Содержание AquaSAFE
Страница 1: ...Uponor AquaSAFE System Installation Guide...
Страница 36: ...30 l Uponor AquaSAFE System Installation Guide...
Страница 54: ...48 l Uponor AquaSAFE System Installation Guide...
Страница 56: ...50 l Uponor AquaSAFE System Installation Guide...
Страница 62: ...56 l Uponor AquaSAFE System Installation Guide...
Страница 68: ...62 l Uponor AquaSAFE System Installation Guide...
Страница 71: ...uponor usa com uponor ca l 65...