background image

-7-

VENT TERMINATION CLEARANCES

A. 

Minimum  4-foot  (1.22m)  clearance 

below or beside any door or window 

that opens.

B. 

Minimum  1-foot  (0.3m)  clearance 

above any door or window that opens.

C. 

Minimum  3-foot  (0.91m)  clearance 

from any adjacent building.

D. 

Minimum  7-foot  (2.13m)  clearance 

from any grade when adjacent to 

public walkways.

E. 

Minimum  2-foot  (0.61m)  clearance 

above any grass, plants, or other 

combustible materials.

F. 

Minimum  3-foot  (0.91m)  clearance 

from an forced air intake of any 

appliance.

G.  Minimum  2-foot  (0.61m)  clearance 

below eves or overhang.

H. 

Minimum 1-foot (0.3m) clearance horizontally from combustible wall.

I. 

Must be a minimum of 3 foot (0.91m) above the roof and 2 foot (0.61m) above the highest point or the roof 

within 10 feet (3.05m).

G

Figure 6

Vent Termination Clearances

THROUGH THE WALL INSTALLATION 

(RECOMMENDED 

INSTALLATION)

Canadian installations must conform to CAN/CSA-B365.  To 

vent the unit through the wall, connect the pipe adapter to 

the exhaust motor adapter. If the exhaust adapter is at least 

18 in.(457mm) above ground level, a straight section of pellet 

vent pipe can be used through the wall. Your heater dealer 

should be able to provide you with a kit that will handle most 

of this installation, which will include a wall thimble that will 

allow the proper clearance through a combustible wall. 

Once outside the structure, a 3 in.(76mm) clearance should 

be maintained from the outside wall and a clean out tee 

should be placed on the pipe with a 90-degree turn away 

from the house. At this point, a 3ft (0.91m) (minimum) section 

of pipe should be added with a horizontal cap, which would 

complete the installation (see FIGURE 7). A support bracket 

should be placed just below the termination cap or one 

every  4ft  (1.22m)  to  make  the  system  more  stable.  If  you 

live in an area that has heavy snowfall, it is recommended 

that the installation be taller than 3ft (0.91m) to get above 

the snowdrift line. This same installation can be used if your 

heater is below ground level by simply adding the clean-out 

section and vertical pipe inside until ground level is reached. 

With this installation you have to be aware of the snowdrift 

line, dead grass, and leaves. We recommend a 3ft (0.91m) 

minimum vertical rise on the inside or outside of the house. 

The “through the wall” installation is the least expensive and 

simplest installation. Never terminate the end vent under a deck, in an alcove, under a window, or between two 

windows. We recommend Simpson Dura-Vent® or Metal-Fab® kits.

THROUGH THE ROOF/CEILING INSTALLATION

When venting the heater through the ceiling, the pipe is connected the same as through the wall, except the 

clean-out tee is always on the inside of the house, and a 3 in.(76mm) adapter is added before the clean-out tee.

You must use the proper ceiling support flanges and roof flashing (supplied by the pipe manufacturer; follow the 

pipe manufacturer’s directions). It is important to note that if your vertical run of pipe is more than 15ft (4.57m), 

the pellet vent pipe size should be increased to 4 in. (102mm) in diameter.

Do not exceed more than 4ft (1.22m) of pipe on a horizontal run and use as few elbows as possible. If an offset 

is required, it is better to install 45-degree elbows rather than 90-degree elbows.

Figure 7

Typical Through The Wall Installation

Содержание KP130

Страница 1: ...he appliance Keep viewing and ash removal doors tightly closed during operation Replace glass with 5mm ceramic glass ONLY IMPORTANT When the hopper lid is open the auger will stop Close the hopper lid...

Страница 2: ......

Страница 3: ...R FUTURE REFERENCE Please read this entire manual before installation and use of this appliance Failure to follow these instructions could result in property damage bodily injury or even death Contact...

Страница 4: ...ced on a non combustible surface or on the ground well away from all combustible materials pending final disposal The exhaust system should be checked monthly during the burning season for any build u...

Страница 5: ...Environmental Protection Agency s crib wood emission limits for wood heaters sold after May 15 2020 Under specific EPA test conditions burning wood pellet fuel this heater has been shown to deliver he...

Страница 6: ...an NFI certified specialist IMPROPER INSTALLATION The manufacturer will not be held responsible for damage caused by the malfunction of a stove due to improper venting or installation Call 800 750 272...

Страница 7: ...m CORNER D Adjacent wall to unit 8 00 203mm ALCOVE E Alcove depth 36 00 914mm 5500 M only F Alcove height 60 00 520mm CLEARANCES Your pellet stove has been tested and listed for installation in reside...

Страница 8: ...the stove use a 3 inch to 4 inch adapter for 4 inch pipe Connection at back of stove must be sealed using Hi Temp RTV Use 4 inch vent if the vent height is over 12 feet or if the installation is over...

Страница 9: ...ction of pipe should be added with a horizontal cap which would complete the installation see FIGURE 7 A support bracket should be placed just below the termination cap or one every 4ft 1 22m to make...

Страница 10: ...ection to the heater SPECIAL MOBILE HOME REQUIREMENTS WARNING Do not install in a sleeping room CAUTION The structural integrity of the mobile home floor wall and ceiling roof must be maintained A wor...

Страница 11: ...a forced draft pressure is required for the combustion process inside your stove it is extremely important that the exhaust system be properly installed and maintained And that when operating your st...

Страница 12: ...at will not properly control the unit When adjusting the Draft Fan setting try only 1 setting above or below the heat setting It is better to leave the stove in the automatic mode ROOM FAN The room fa...

Страница 13: ...the preselected desired heat range setting 1 to 5 and the minimum heat range setting of 1 The T Stat will not turn the stove on and off When the desired room temperature has been reached and the T Sta...

Страница 14: ...w LEDs will be off 5 Hopper Switch Test The display will show hppr The ON LED is lit If the hopper switch is open lid is open the HEAT RANGE LED will turn on If the lid is closed the HEAT RANGE LED wi...

Страница 15: ...the heat exchanger in the stove reaches the factory preset temperature Attempts to achieve heat output rates that exceed heater design specifications can result in permanent damage to the heater First...

Страница 16: ...ck panel or opening the exhaust system for any inspection cleaning or maintenance work Never perform any inspections cleaning or maintenance on a hot stove Do not operate stove with broken glass leaka...

Страница 17: ...We recommend using a high quality glass cleaner Should a build up of creosote or carbon accumulate you may wish to use 000 steel wool and water to clean the glass DO NOT use abrasive cleaners DO NOT p...

Страница 18: ...re that the viewing door is closed and sealed properly If not adjust door catch and or replace door gaskets Check that all outside connections are clear of any obstructions Check the exhaust system cl...

Страница 19: ...tor This indicates that the stove is in normal operation and is running in the automatic mode However either the draft fan or room fan setting is manually configured Flashing Draft Fan Setting Indicat...

Страница 20: ...18 GRAY BLACK Wiring Diagram CORRECT WRONG Ensure the wires are connected to the bottom two prongs of the hopper switch as shown...

Страница 21: ...ght 1 12 69787 Hopper Assembly 1 13 80491 MIcroswitch 1 14 83541 4 40 Bolt 2 15 893039 Remote Sensor Bracket 1 16 25480MB Access Panel 1 17 80461 Power Supply Cord 1 18 80462 Receptacle 3 Prong 1 19 8...

Страница 22: ...20 9 3 2 1 5 6 4 7 8 10 Parts Diagram 47 46 48 49 50...

Страница 23: ...07 Date _____________________ Engineer Name ________________________________ License No ____________________________________ Company _____________________________________ Telephone No _______________...

Страница 24: ...s pi ces d tach es Gardez ce manuel dans un lieu s r pour toute consultation ult rieure Lorsque vous nous crivez donnez toujours le num ro de mod le complet qui se trouve sur la plaque signal tique fi...

Страница 25: ...____________________________ Service de 07 Date _____________________ Nom de l ing nieur ____________________________ N de licence _________________________________ Compagnie _________________________...

Страница 26: ...e Droit 1 12 69787 Assembl e Hopper 1 13 80491 Micro Interrupteur 1 14 83541 4 40 Bolt 2 15 893039 Support de capteur distance 1 16 25480MB Panneau D acc s 1 17 80461 Cordon D alimentation 1 18 80462...

Страница 27: ...20 Sch ma des pi ces 9 3 2 1 5 6 4 7 8 10 47 46 48 49 50...

Страница 28: ...SOSTAT MARRON MARRON NOIR BLANC ROUGE BLEU ORANGE PRISE MOLEX AU CIRCUIT IMPRIM PCB PRINCIPAL NOIR NOIR NOIR BLANC BLANC SOUFFLANTE DE DISTRIBUTION VENTILATEUR D VACUATION THERMISTOR Sch ma de c blage...

Страница 29: ...eux fois par seconde Cela indique que le po le fonctionne normalement et qu une condition de temp rature excessive existe provoquant l arr t du combustible Indicateur de r glage du niveau de chaleur H...

Страница 30: ...e V rifiez que le raccordement du pressostat au foyer ne contienne aucune cendre ni obstruction Le syst me vis sans fin est bloqu ou il y a une vo te de combustible dans la tr mie qui emp che le combu...

Страница 31: ...le et d paisseur correctes doivent tre utilis es NE substituez PAS le verre avec des mat riaux alternatifs Contactez votre revendeur autoris pour obtenir ce verre R installez le nouveau verre en le fi...

Страница 32: ...fi peut effectuer ces travaux Il est aussi recommand qu avant chaque saison de chauffage le syst me complet soit inspect nettoy et si n cessaire r par par un professionnel Pour nettoyer la chemin e d...

Страница 33: ...sur le bouton OFF arr t et ensuite de nouveau sur le bouton ON marche pour commencer une nouvelle s quence de mise en route 2 Si le po le a refroidi il se r initialisera l tat OFF arr t ce moment l vo...

Страница 34: ...de l eau sal e 11 Bois non s ch ou 12 Produits du papier carton contreplaqu ou panneau de particules L interdiction de br lage de ces mat riaux n interdit pas l utilisation d allume feu compos s de pa...

Страница 35: ...fin se met en marche plein r gime Si le fusible de la vis sans fin n a pas saut et que le circuit de d tection fusible fonctionne le voyant DEL Heat Range du degr de chaleur sera allum et les trois au...

Страница 36: ...justez le r glage du ventilateur de tirage essayez seulement 1 r glage au dessus ou en dessous du r glage de chaleur Il est pr f rable de laisser le po le en mode automatique VENTILATEUR DE LA PI CE L...

Страница 37: ...rage forc e est n cessaire au processus de combustion l int rieur de votre po le il est extr mement important que le syst me d vacuation soit install correctement et maintenu Et que lors du fonctionne...

Страница 38: ...ionn de la plage de chaleur d sir e 1 5 et le r glage de la plage de chaleur minimale de 1 Le T Stat n allumera ni ne teindra le po le Lorsque la temp rature ambiante souhait e est atteinte et que le...

Страница 39: ...nag e Apr s le d m nagement tous les vents doivent tre r install s et fix s fermement L air ext rieur est obligatoire pour l installation d une maison mobile Consultez votre revendeur lors de l achat...

Страница 40: ...rd en T de regard devra tre plac sur le tuyau avec une sortie 90 degr s hors de la maison ce point une partie de tuyau de 3 pieds 0 91m minimum devra tre ajout e avec un couvercle horizontal qui devra...

Страница 41: ...e doit tre scell en utilisant un produit vulcanis RTV pour temp ratures lev es Utilisez une ventilation de 4 pouces si la hauteur de ventilation est sup rieure 12 pieds ou si l installation se trouve...

Страница 42: ...re minimum plus grand afin d obtenir un acc s commode au panneau de contr le FIGURE 3 D GAGEMENTS DE LA PAROI LAT RALE INSTALLATION EN PARALL LE FIGURE 4 D GAGEMENTS DE LA PAROI LAT RALE INSTALLATION...

Страница 43: ...cialiste certifi NFI NE CONNECTEZ PAS CETTE UNIT UN CONDUIT OU CIRCUIT DE DISTRIBUTION D AIR INSTALLATION INCORRECTE Le fabricant ne sera pas tenu responsable des dommages caus s par un dysfonctionnem...

Страница 44: ...vos pellets dans un endroit sec NE stockez PAS le carburant dans les d gagements d installation de l appareil ou dans l espace requis pour faire le plein et enlever les cendres Cela pourrait provoque...

Страница 45: ...oivent tre jet es dans un conteneur m tallique avec un couvercle d ajustement serr Le conteneur ferm dans lequel se trouvent les cendres devra tre plac sur une surface non combustible ou sur le sol bi...

Страница 46: ...reil n est pas destin tre utilis en tant que principale source de chaleur U S Environmental Protection Agency Certifi aux normes d missions de 2020 particules CONSERVEZ CES INSTRUCTIONS CE MANUEL VOUS...

Отзывы: