17.System-related Settings and Operations
130
3. Input / output test
IInput and output, and the input pulse frequency of the PUI (when the option is mounted)
can be checked.
Press
/
to start each test.
All input and output pins are tested as follows:
1. All outputs are turned on for approx. 0.5 sec.
2. Outputs are turned on one by one for approx. 0.5 sec. in the order
of 17 ~ 24, and 42 ~ 49.
3. The condition of each input pin is displayed in hexadecimal.
The relationship between displays and input pins is as follows:
When the PUI option is mounted, the input pulse frequency is
displayed.
(The number of pulses changing in 1 sec. is checked to display the
frequency.)
IN
:
×× ×× ××
ON = Hexadecimal
OFF =
0
}
}
}
( 1 )
( 2 ) ( 3 )
)
01 02 04 08 10 20 40 80
(
1
)
・・
・
・
2 3 4 5 6 7 8 9
(
2
)
・・
・
・
27 28 29 30 31 32 33 34
(
3
)
・・
・
・
11 12 13 14 36 37 38 39
Pin No.
)
Display
(by adding the statement
on the left-hand side.)
0 ~ 9
10 ~ 15
0 ~ 9
A ~ F
→
→
Decimal
Hexadecimal
The hexadecimal display is as follows: