54
Holding
Register
Type
Value
Comments
40020
Read / Write 0 to 10V Cool
Span
1 to 6°F degrees in 1°F degree Steps
0.5 to 3°C degrees in 0.5°C degrees Steps
Value / 10 (e.g. Cool Span of 1°C = 10)
40021
Read / Write Auto Off
Timer
0 = 0ff
1 to 10 Hours. (0.5 hour steps)
Value / 10 (e.g. 3 Hour Auto Off Timer = 30)
40022
Read /Write
Unoccupied
Heat Setpoint
0 = Off
41 to 86°F in 1°F Steps
5 to 30°C in 0.5°C Steps
Value / 10 ( e.g. 17°C Unoccupied Heat = 170)
40023
Read / write Unoccupied
Cool Setpoint
0 = Off
41 to 86°F in 1°F Steps
5 to 30°C in 0.5°C Steps
Value / 10 ( e.g. 28.5°C Unoccupied Cool =
285)
Содержание SmartSense SMART 3000