WIRING INFORMATION
Table 2
Terminal
Function
C
24V AC Common or Neutral
R
24V AC Active - This voltage is switched back through the relays
Hi
Indoor Fan High Speed (NOT Used in Single fan speed mode -
Sw1 = OFF)
Med
Indoor Fan Medium Speed (NOT Used in Single fan speed mode -
Sw1 = OFF)
Low
Indoor Fan Low Speed (Used in single and three fan speed mode)
Y
Compressor or Cool - (Based on Sw2 setting)
W - O/B
Reversing Valve or Heat - (Based on Sw2 setting)
A1 – Cool
0 to 10V Output for Cooling (Typically used to control modulating
valves)
A2 – Heat
0 to 10V Output for Heating (Typically used to control modulating
valves)
A3 – Fan
0 to 10V Modulating Output for Indoor DC Fan