22
selected the 0 to 10V output will be fixed at 6.6V DC. High speed is set to 10V DC.
The Installer Menu provides the following settings for the control of the three 0
to 10V outputs.
Span
This is the setting for the outputs maximum value. It sets how aggressive the 0 to
10V will move for a given temperature change. The range is 0 to 9°F degrees
(0 to 5°C degrees) .
Time Interval
Time interval sets the running average calculation time. The smaller the number
the faster the 0 to 10V output will respond to room temperature changes. The
range is 10 to 300 seconds.
Direction
Forward action 0V = 0% open and 10V = 100% open; reverse action sets 0V =
100% open and 10V = 0% open.
Minimum Value
Rather than start the output at 0V, when the output is called it will immediately
jump to this value. It will then vary the output to maximum. When approaching
the setpoint the value will drop from the minimum value to 0V in 1 step. This
setting is particularly useful for fan control as it will not permit the fan to run too
slowly when close to setpoint.