45
Option
Setting
18
Cool Span
1.0 to 6.0°F degrees/0.5 to 3.0°C degrees in 1°F
degrees/0.5°C degrees steps
Data format: Fan span * 10
19
0 to 10V Cool Interval (PI)
10 to 300 seconds 10 seconds steps
(60 seconds default)
20
0 to 10V Cool Direction
0: 10V is 100% open (forward acting)
1: 0V is 100% open (reverse acting)
21
0 to 10V Cool Minimum
Voltage
0 to 10V
Data format: 0 to 10V Cool minimum value * 10
22
Auto Off Timer
0: No auto off timer
1 to 10 hours in 0.5 hours steps
Data format: hour * 10
23
Unoccupied Heat
Setpoint
0: OFF
41 to 86°F /5 to 30°C in 1°F degrees/0.5°C degrees
steps
24
Unoccupied Cool
Setpoint
0: OFF
41 to 86°F /5 to 30°C in 1°F degrees/0.5°C degrees
steps