- 27 -
Mode No.
Hold input function setting, display blank, lowest digit display
7
A B C D E
7.0 0 0
Lowest digit display
0:Real
1:Fixed at 0
2:0 or 5
Display blank
0:Normal display
1:Blank display
Hold input function setting
0:No use
1:Peak hold
2:Bottom hold
3:Hold
4:Reverse-rotation input (differential rate measurement)
〔Hold input function setting〕
Set a function when ON(short) did terminal stand 2
–
3
0:No use
Hold input is invalid.
1:Peak hold
Between ON,
it updates a highest value indication level while blinking.
2:Bottom hold
Between ON,
it updates a smallest value indication level while blinking.
3:Hold
Between ON, It displays a current value while blinking.
4:Reverse-rotation input (differential rate measurement)
It functions as Reverse-rotation input.
(This function becomes invalid other than differential rate measurement)
〔Display blank〕
When I set it to 1, A measured value(7segment LED) and each lamp display
it and do not turn on. (But preset put lamp OUT1-4 is excluded)
〔Lowest digit display〕
The form of indication for the least significant digit (digit on the right end)
is selected.
0:Real・・・・・・・・Synchronized at the sampling time.
1:Fixed at 0 ・・・・Always, "0".
2:0 or 5・・・・・・・0-4 are expressed as 0, and 5-9 as 5.