- 21 -
Mode No.
A-input:Setting of scaling data
1
A B C D E
1.1 0 0 0
Scaling data:0001
–
9999
(Do not set 0000)
Please set the pulse rate (scaling data) of the sensor.
4 digit of numerical value to set with this mode,
and please input Exp.value of
Mode No. 2. Then 1×10
-9
~ 9999” can set the magnification per 1 signal.
Measuring types:08(Passing time measurement), set it in unit “mm/p”
Measuring types:09~12(shot speed), set the distance between the sensor.
〔Ex.〕Using a flow sensor which emits 1 pulse per 1.234mL,
the cumulative total flow in liters can be expressed using
the following conversion.
1.234mL 0.001234L 1234 × 10
-6
Scaled to the desired unit (L)
4 digits(Scaling data) Exp. Value(exponent)
A B C D E
Mode No.1 1.1 2 3 4
A B C D E
Mode No.2 2.6 * * *
The above is based on the example of flow rate measurement, while for
examples of conversion value, refer to next page.
For ratio-measurement, sensor is connected to A and B for each 1 piece,
then, set Mode No.
“
3
”
and
“
4
”
.