84
Boiler
Model
Burner
Input
(GPH)
Burner
Model
Nozzle
Head
Setting
Air
Setting
Pump
Pressure
(PSI)
Air Tube
Type
Insertion
Depth
(Inch)
Approx.
Shipped
CO
2
(%)
Baffle
Location
(pass)
Approx.
Stack Temp.
Increase
Without
Baffles °F
(2)
Approx.
Breech
Pressure
(" w.c.)
(3)
Baffles IN
Approx.
Overfire
Pressure
(" w.c.)
(3)
Baffles
OUT
Approx.
Overfire
Pressure
(" w.c.)
(3)
MPO-IQ84
0.60
EZ-LF 0.50 x 60AS
Danfoss
1.0
30
150
12D
2-5/8
11.5
3
rd
52
0
+0.040
+0.020
MPO-IQ115
0.82
EZ-LF 0.65 x 60AS
Danfoss
0.75
65
150
12D
2-5/8
11.5
2
nd
& 3
rd
84
0
+0.040
+0.020
MPO-IQ147
1.05
EZ-66
0.85 x 45AS
Danfoss
2.0
40
150
Conical
Wrap
2-5/8
11.5
2
nd
65
0
+0.040
+0.020
MPO-IQ189
1.35
EZ-66
1.10 x 45B
Delavan
3.5
50
150
Conical
Wrap
2-5/8
11.5
2
nd
39
0
+0.040
+0.030
MPO-IQ231
1.65
EZ-66
1.35 x 45B
Hago
5.5
60
150
Conical
Wrap
2-5/8
11.5
2
nd
18
0
+0.050
+0.030
Notes
(2)
The increased stack temperature with the baffles removed is an approximation, based on a constant supply temperature of 180°F and 11.5% CO
2
. Actual field
conditions may be different.
(3)
These values are minimum and could be as much as -.03" w.c., more without impacting performance. Pressures based on 11.5% CO
2
. Example: MPO-IQ231
could have a breech pressure of -.03" w.c. and an overfire pressure of .020" w.c.
4) Single stage fuel pump is standard, two-stage fuel pump is optional. Burner manufacturer has preset single stage fuel pump to settings shown in table above.
Two-stage fuel pump is factory set at 140 PSI and must be readjusted to settings shown above during burner start-up.
TABLE 15C: CARLIN EZ BURNER SPECIFICATIONS - CHIMNEY VENT
TABLE 16: BECKETT Nx BURNER SPECIFICATIONS - DIRECT VENT
Boiler Model
Burner
Input
(GPH)
Head /Air
Adjustment
(setting)
Nozzle
Pump
Pressure
(PSI)
Approx.
Shipped
CO
2
(%)
Baffle
Location
(pass)
Approx. Stack
Temp. Increase
Without Baffles
°F
(2)
Baffles
IN
Minimum
Overfire
Pressure
(" w.c.)
(3)
Baffles OUT
Minimum
Overfire
Pressure
(" w.c.)
(3)
Baffles
IN
Minimum
Breech
Pressure
(" w.c.)
(3)
Baffles
OUT
Minimum
Breech
Pressure
(" w.c.)
(3)
MPO-IQ147
1.05
2.75
0.75 - 60°W
Delavan
180
11.5
2
nd
75
+0.06
+0.045
+0.045
+0.03
MPO-IQ189
1.35
1.00
1.00 - 45°B
Hago
180
11.5
2
nd
70
+0.10
+0.05
+0.08
+0.04
MPO-IQ231
1.65
2.25
1.25 - 45°B
Hago
180
11.5
2
nd
23
+0.07
0
+0.06
+0.02
Notes
(2)
The increased stack temperature with the baffles removed is an approximation, based on a constant supply temperature of 180°F and 11.5% CO
2
.
Actual field values may be different.
(3)
These values are representative for max vent and air intake piping conditions @ 180°F supply water temperature and 11.5% CO
2
. Actual field values
may be different.
4) Single stage fuel pump is standard, two-stage fuel pump is optional. Burner manufacturer has preset single stage fuel pump to settings shown in
table above. Two-stage fuel pump is factory set at 140 PSI and must be readjusted to settings shown above during burner start-up.
xV. BURNER SPECIFICATIONS (continued)
Содержание MPO - IQ
Страница 6: ...6 Figure 1 MPO IQ84 Thru MPO IQ231 Water Boiler ...
Страница 22: ...22 Figure 11 Boiler Removal from Skid III UNIT PAK BOILER ASSEMBLY TRIM CONTROLS continued ...
Страница 27: ...27 Figure 13A Recommended Water Piping for Circulator Zoned Heating Systems IV WATER Boiler PIPING continued ...
Страница 28: ...28 Figure 13B Recommended Water Piping for Zone Valve Zoned Heating Systems IV WATER Boiler PIPING continued ...
Страница 42: ...42 Figure 28A Schematic Wiring Diagram VII ELECTRICAL continued ...
Страница 43: ...43 Figure 28B Schematic Wiring Diagram Burner Options VII ELECTRICAL continued ...
Страница 44: ...44 Figure 28C Ladder Diagram VII ELECTRICAL continued ...
Страница 70: ...70 Bare Boiler Assembly XIV Repair Parts continued ...
Страница 72: ...72 Jacket Assembly XIV Repair Parts continued ...
Страница 74: ...74 MPO IQ84 Thru MPO IQ231 Water Boilers Trim and Controls XIV Repair Parts continued ...
Страница 78: ...78 Beckett AFG Burner XIV Repair Parts continued ...
Страница 80: ...80 Beckett NX Burner XIV Repair Parts continued ...
Страница 92: ...92 U S Boiler Company Inc P O Box 3020 Lancaster PA 17604 1 888 432 8887 www usboiler net ...