SECTION 5 – INSTALLATION ANd prOgrAmmINg
2014-MAY-02 REV. 0 PAGE 5-13
dETECTION CIrCUIT CABLES (Continued)
FIgUrE 5-32
dETECTION CIrCUIT - EmA
009294
FIgUrE 5-33
dETECTION CIrCUIT – SpOT THErmAL dETECTOrS
009223
FIgUrE 5-34
dETECTION CIrCUIT - LINEAr dETECTOr
009224
review complete installation to verify correctness. If any
of the following INCOrrECT INSTALLATION examples are
found adjust as needed.
INCORRECT INSTALLATIONS
CAUTION
Do not use an EOL Device on a branch because complete
detection circuit will not be monitored. (See Figure 5-35 and
5-36). Double branching is not allowed. (See Figures 5-35 thru
5-37). Failure to comply may cause the system to not function
properly.
FIgUrE 5-35
INCOrrECT EmA ANd EOL INSTALLATION
009297
FIgUrE 5-36
INCOrrECT EmA ANd EOL INSTALLATION
009298
CAUTION
Only one EMA may be installed from a detection circuit tee on a
single branch circuit. If multiple EMAs are to be installed, addi-
tional branches on the main trunk will be required (one EMA
per branch). Incorrect installations will cause the system to not
function properly. See Figure 5-37.
FIgUrE 5-37
INCOrrECT EmA INSTALLATION
009299
CHECKFIRE 210
Detection and Actuation System
MUST INSTALL EMA(S)
IF USED PRIOR TO
OTHER DEVICES
LIMIT: ONE EMA PER
BRANCH
BRANCH
TERMINATOR
BRANCH
CIRCUIT
INSTALLATION
MAIN TRUNK
INSTALLATION
EOL DEVICE
END OF
MAIN TRUNK
NO EOL DEVICE
ON BRANCH
NO DOUBLE
BRANCHING
EMA MUST BE
ON SINGLE USE
BRANCH
NO EOL DEVICE
ON BRANCH
NO DOUBLE
BRANCHING
EMA MUST BE
ON SINGLE USE
BRANCH
NO DOUBLE
BRANCHING
Содержание ANSUL CHECKFIRE 210
Страница 2: ......
Страница 6: ...REVISION RECORD PAGE 2 REV 0 2014 MAY 09 NOTES CHECKFIRE 210 Detection and Actuation System...
Страница 12: ...SECTION 1 SYSTEM DESCRIPTION PAGE 1 4 REV 0 2014 MAY 02 NOTES CHECKFIRE 210 Detection and Actuation System...
Страница 26: ...SECTION 2 COMPONENTS PAGE 2 14 REV 0 2014 MAY 02 CHECKFIRE 210 Detection and Actuation System NOTES...
Страница 34: ...SECTION 3 USER INTERFACE PAGE 3 8 REV 0 2014 MAY 02 NOTES CHECKFIRE 210 Detection and Actuation System...
Страница 46: ...SECTION 4 SYSTEM PLANNING PAGE 4 12 REV 0 2014 MAY 02 NOTES CHECKFIRE 210 Detection and Actuation System...
Страница 108: ...SECTION 7 IN CASE OF FIRE PAGE 7 2 REV 0 2014 MAY 02 NOTES CHECKFIRE 210 Detection and Actuation System...