SECTION 5 – INSTALLATION ANd prOgrAmmINg
2014-MAY-02 REV. 0 PAGE 5-11
Bracket mounting Instructions (Continued)
FIgUrE 5-25
EmA INSTALLEd IN BrACKET
009219
ELECTrIC-pNEUmATIC ACTUATOr INSTALLATION
The Electric-Pneumatic Actuator (Part No. 439569) installs on
an expellant gas cartridge and can be used as an electronic
and/or pneumatic actuation device, see Figure 5-26. The
actuator includes a preventor to reduce the possibility of install-
ing actuator with the puncture pin not completely retracted,
see Figure 5-27. Do not bend or remove the preventor; it is
required for correct operation of the actuator.
The CHECKFIRE 210 System can actuate a maximum of ten
Electric-Pneumatic Actuators.
Visually confirm lubrication of the upper o-ring and push punc-
ture pin down several times to confirm ease of movement.
Make sure pin is completely retracted.
FIgUrE 5-26
ELECTrIC-pNEUmATIC ACTUATOr
009168
WArNINg
!
Before attaching Electric-Pneumatic Actuator to expellant gas
cartridge, verify the cartridge is properly secured and confirm
puncture pin is in the completely retracted position. See Figure
5-27. If puncture pin is not completely retracted, the seal can
become damaged or pierced, which can result in system actu-
ation or serious personal injury or death.
FIgUrE 5-27
rETrACT ACTUATOr pUNCTUrE pIN
009220
1. To install the actuator, slide the unit onto the expellant
gas cartridge from the side. (Cartridge must be properly
secured.) Slide preventor underneath cartridge threads and
thread actuator on cartridge. See Figure 5-28.
FIgUrE 5-28
SLIdE ACTUATOr ONTO CArTrIdgE
009221
2. wrench-tighten actuator base (SS) to cartridge. Note:
wrench grip is above preventor. See Figure 5-28.
3. Turn cartridge in cartridge bracket (loosen as needed) so
expellant gas outlet is in desired orientation, then re-secure
cartridge in bracket.
CHECKFIRE 210
Detection and Actuation System
PREVENTOR COLOR CHANGED FOR CLARITY
PREVENTOR
SLIDES UNDER
THREADS
wRENCH
GRIP
PIN NOT RETRACTED
PIN COMPLETELY RETRACTED
PREVENTOR
1/4 IN.
(6.4 mm)
CONFIRM PULL PIN
IS ACCESSIBLE
CONNECTS TO:
DETECTION
CIRCUIT BRANCH
PREVENTOR
ACTUATOR BASE
(STAINLESS
STEEL (SS))
ACTUATOR
SwIVEL BODY
OUTLET FOR
ExPELLANT GAS
TO AGENT TANK
ACTUATOR CAP
(IF REMOVED KEEP
FOR MAINTENANCE)
1/4 IN. NPT BRASS PLUG
(OPTIONAL PNEUMATIC
ACTUATION HOSE PORT –
TwO PLACES)
Содержание ANSUL CHECKFIRE 210
Страница 2: ......
Страница 6: ...REVISION RECORD PAGE 2 REV 0 2014 MAY 09 NOTES CHECKFIRE 210 Detection and Actuation System...
Страница 12: ...SECTION 1 SYSTEM DESCRIPTION PAGE 1 4 REV 0 2014 MAY 02 NOTES CHECKFIRE 210 Detection and Actuation System...
Страница 26: ...SECTION 2 COMPONENTS PAGE 2 14 REV 0 2014 MAY 02 CHECKFIRE 210 Detection and Actuation System NOTES...
Страница 34: ...SECTION 3 USER INTERFACE PAGE 3 8 REV 0 2014 MAY 02 NOTES CHECKFIRE 210 Detection and Actuation System...
Страница 46: ...SECTION 4 SYSTEM PLANNING PAGE 4 12 REV 0 2014 MAY 02 NOTES CHECKFIRE 210 Detection and Actuation System...
Страница 108: ...SECTION 7 IN CASE OF FIRE PAGE 7 2 REV 0 2014 MAY 02 NOTES CHECKFIRE 210 Detection and Actuation System...