SECTION 5 – INSTALLATION ANd prOgrAmmINg
PAGE 5-30 REV. 0 2014-MAY-02
CHECKFIRE 210
Detection and Actuation System
TABLE 5-3: mANUAL prOgrAmmINg OpTIONS (Continued)
TABLE 5-4: dOWNLOAd EVENT HISTOrY LOg
rLY-11, relay #2, Shutdown/Alarm
RLY-11 changes the function of Internal Relay #2 between a
Shutdown Relay (default programming – OFF) and an Alarm
Relay (ON). when programmed to the Shutdown functionality
the relay contacts transfer when TD1 expires. The latching
relay will not transfer back to normal until the CHECKFIRE
210 System is reset from the Post Release Activated condi-
tion.
when programmed to the Alarm Relay functionality, the initi-
ation of an alarm condition transfer the relay contacts. The
relay will return to normal once the alarm condition clears.
1. If the system plan requires Relay #2 to function as an
Alarm Relay and RLY-11 is OFF, push programming
button until RLY-11 is selected (pulsing at a rate of 1 x 1
second).
2. Press and hold the programming button for more than 1
second to turn ON the LED and specify the Alarm Relay
function. The 1 x 1 second pulse is now twice as long.
3. Push the programming button to move to the next LED
and confirm
• RLY-11 is steady-on
• PSF-1 is pulsing 1 x 1 second.
4. Save the ICM programming change.
Reset to Normal: Press and hold “DELAY/Reset/
Silence” button for 3 seconds; Green and Red LEDs are
steady-on for 1 second; then Amber LEDs are steady-on
for 1 second; at end sounder quickly pulses 3 times.
1. PUSH PB
UNTIL
RLY-11 IS
SELECTED
2. PRESS
AND HOLD
PB TO
CHANGE
SETTING
3. PUSH PB
TO MOVE
TO NExT LED
AND CONFIRM
CHANGE IS
CORRECT
4. SAVE CHANGE
The Event History Log of the CHECKFIRE 210 System can
be downloaded as a text file directly to a USB memory device
(by others) without connection to a personal computer (PC).
The USB memory device may then be plugged into a PC to
print or save the file to a different location.
• Allows service personnel to retrieve programming and
Event History Log without connecting a PC to ICM.
• Allows service personnel to save a text file which helps
verify maintenance and operation of the CHECKFIRE 210
System.
Communication adapter cable (by others) is required to
connect a standard USB memory device to the mini USB port
on the ICM. Items needed:
1. Interface Cable: USB A Female receptacle and Mini A
plug x 4 in. (102 mm) long
2. Standard USB memory device
Содержание ANSUL CHECKFIRE 210
Страница 2: ......
Страница 6: ...REVISION RECORD PAGE 2 REV 0 2014 MAY 09 NOTES CHECKFIRE 210 Detection and Actuation System...
Страница 12: ...SECTION 1 SYSTEM DESCRIPTION PAGE 1 4 REV 0 2014 MAY 02 NOTES CHECKFIRE 210 Detection and Actuation System...
Страница 26: ...SECTION 2 COMPONENTS PAGE 2 14 REV 0 2014 MAY 02 CHECKFIRE 210 Detection and Actuation System NOTES...
Страница 34: ...SECTION 3 USER INTERFACE PAGE 3 8 REV 0 2014 MAY 02 NOTES CHECKFIRE 210 Detection and Actuation System...
Страница 46: ...SECTION 4 SYSTEM PLANNING PAGE 4 12 REV 0 2014 MAY 02 NOTES CHECKFIRE 210 Detection and Actuation System...
Страница 108: ...SECTION 7 IN CASE OF FIRE PAGE 7 2 REV 0 2014 MAY 02 NOTES CHECKFIRE 210 Detection and Actuation System...