SECTION 8 – RECHARGE, INSPECTION, AND MAINTENANCE
2014-MAY-02 REV. 0 PAGE 8-3
RECHARGE (Continued)
FIGURE 8-4
RETRACT ACTUATOR PIN
009220
b. Re-install Electric-Pneumatic Actuator(s) on expel-
lant gas cartridge(s). See Section 5 – Installation and
Programming, page 5-11 and 5-12 for correct proce-
dure.
9. Test system and place into service by completing all steps
in Section 6 - Operational Test and Place in Service, prior
to proceeding to Step 10.
10. Complete steps 1 – 4 in the Maintenance Section.
11. Confirm all system equipment has been properly serviced
and recharged, and visual inspection seals are in place on
all EMAs and Display Module.
12. Record date of recharge on tag and in permanent record
file. Notify operating personnel system is back in service.
INSPECTION AND MAINTENANCE
To help ensure the CHECKFIRE 210 Detection and Actuation
System will operate as intended, proper inspection and mainte-
nance procedures must be performed at the specified intervals.
DAILY INSPECTIONS
The vehicle/equipment operator must check the system daily
by visually verifying:
• Power LED is Green and steady-on with external/dual power
or pulsing 1 x 3 seconds with internal power, see Figure 8-5
• All other LEDs are off (not steady-on or pulsing)
• Sounder is silent
• No apparent damage to any components
If any other conditions exist, contact the local Authorized
ANSUL Distributor or a person who has been trained and
authorized by Tyco Fire Protection Products to perform inspec-
tion and maintenance service on the CHECKFIRE 210 System.
FIGURE 8-5
NORMAL CONDITION
009275
MAINTENANCE
To help ensure the system will operate as intended, mainte-
nance shall be performed semi-annually or sooner, depending
on the operating and/or environmental conditions. Maintenance
should be performed by an Authorized ANSUL Distributor or
a person who has been trained and authorized by Tyco Fire
Protection Products to perform maintenance checks.
Visually inspect system to confirm it is adequate for the equip
-
ment hazard areas.
If system is displaying faults, go to Section 9 – Troubleshooting
prior to continuing Maintenance.
1. Check condition of the CHECKFIRE 210 Display Module.
a. Confirm securely mounted, either in the CHECKFIRE
110/210 Mounting Bracket or surface mounted. Verify
all fasteners are tight and display module enclosure nut
is hand-tight.
b. If secured in bracket, check bracket for damage or wear
to ratchet teeth.
c. Check display module for damage or undue wear.
2. Check condition of CHECKFIRE 210 Interface Control
Module (ICM).
a. Confirm CHECKFIRE 210 Mounting Plate is securely
mounted and CHECKFIRE ICM is securely affixed to
Mounting Plate.
b. Confirm cable connections to ICM receptacles are tight
(hand-tighten only). Push in and re-tighten to verify.
3. Check cable connectivity and integrity.
a. Confirm cable connections are tight (hand-tighten only).
Push in and re-tighten to verify.
b. Inspect all cables and connections for wear, abrasion or
other physical damage.
c. Confirm all cables are properly secured within 1 ft
(0.3 m) on both sides of each connection and every 3 ft
(0.9 m) along cable length.
CHECKFIRE 210
Detection and Actuation System
PIN NOT RETRACTED
PIN COMPLETELY RETRACTED
PREVENTOR
1/4 IN.
(6.4 mm)
WITH ExTERNAL/DUAL
POWER, LED IS GREEN
STEADY-ON
WITH INTERNAL
POWER, LED IS
PULSING GREEN
1 x 3 SECONDS
Содержание ANSUL CHECKFIRE 210
Страница 2: ......
Страница 6: ...REVISION RECORD PAGE 2 REV 0 2014 MAY 09 NOTES CHECKFIRE 210 Detection and Actuation System...
Страница 12: ...SECTION 1 SYSTEM DESCRIPTION PAGE 1 4 REV 0 2014 MAY 02 NOTES CHECKFIRE 210 Detection and Actuation System...
Страница 26: ...SECTION 2 COMPONENTS PAGE 2 14 REV 0 2014 MAY 02 CHECKFIRE 210 Detection and Actuation System NOTES...
Страница 34: ...SECTION 3 USER INTERFACE PAGE 3 8 REV 0 2014 MAY 02 NOTES CHECKFIRE 210 Detection and Actuation System...
Страница 46: ...SECTION 4 SYSTEM PLANNING PAGE 4 12 REV 0 2014 MAY 02 NOTES CHECKFIRE 210 Detection and Actuation System...
Страница 108: ...SECTION 7 IN CASE OF FIRE PAGE 7 2 REV 0 2014 MAY 02 NOTES CHECKFIRE 210 Detection and Actuation System...