Page
1
from
8
92329300
8
_09_00
2
GENERAL
o
This device is used indoors
(
ta 40 C
)
in places
where emergency luminaires are needed. Each
device must be permanently connected to mains
power supply
.
The GR-292/M/HL/ADR is
suitable for corridors lighting and the GR-
293/M/HL/ADR for open area lighting. In normal
operation the battery is charging. In case of a
mains power supply failure, the device enters
emergency mode and the illumination LED turns
on. When the mains power supply is restored,
the device turns to normal operation.
The battery charging is completely controlled
.
In
this case, is
achieved the perfect battery
maintenance
,
as well as the elongation of its
duration
.
When the battery has completely
charged
,
it charges with a maintenance current.
The device enters this mode when the mains
power supply has failed
and battery has lost its
Battery Cut-off
Battery Charging
Battery charge failure due to shortcut
The recharging device will recharge the battery
normally after the short circuit is removed and the
batterie(s) are reinstalled.
Thank you for your trust in our products
Olympia Electronics - European manufacturer
ADDRESSABLE SELF TESTING NON-MAINTAINED EMERGENCY CEILING MOUNTED LUMINAIRES
OPERATION VOLTAGE
MAX. SUPPLY CURRENT
220-240V AC / 50-60Hz
19.5mA AC
TECHNICAL CHARACTERISTICS
(for LED MODULE specifications see page 8)
GR-292/M
/
HL/ADR
GR-293/M/HL/ADR
MAXIMUM POWER CONSUMPTION
4.9W / 5.2 VA
BATTERY
4.8V/4Ah, NiMH (4KRMT 23/62)
U-OUT
6V
prolonged staring into the luminaire at a distance closer than 0.4m is not expected.
E = 718 lux.
thr
Do NOT stare at operating light source.The luminaire should be positioned so that
INSULATION BETWEEN SUPPLY & CONTROL TERMINALS
INSULATION BETWEEN SUPPLY & BATTERY CIRCUIT
Basic insulation
Basic insulation
500V
BATTERY PROTECTION
WORKING VOLTAGE AT WHICH THE INSULATION IS DESIGNED
BATTERY VOLTAGE RANGE
BATTERY CHARGE CURRENT RANGE
BATTERY DISCHARGE CURRENT RANGE
BATTERY SUPPLY CURRENT DURING EMERGENCY
Deep discharge and overcharge protection
4-6V
130 - 200mA (normal charge) / 20 - 30mA (trickle charge)
550 - 730mA
(Vbat=4.8V):650mA
CHARGE TIME
INDICATIONS - CONTROLS
MINIMUM DURATION
LIGHT SOURCE
24 hours
1 white
power LED
Charge, lamp fault, battery fault
,
TEST button
3 hours
RELATIVE HUMIDITY
CONSTRUCTION MATERIAL
EXTERNAL DIMENSION
WEIGHT
GUARANTEE
Up to 95%
ABS/PC
3 years
(1
year for the battery
)
737gr.
Ø125 x 72 mm
OPERATION TEMPERATURE RANGE
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
EMERGENCY ILLUMINATION
IP20
2.3W/760mA
o
5 to 40 C
EN 60598-1, EN 60598-2-22, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3
330lm
Controlgear is suitable for LED module only
The controlgear has mains-connected windings of transformer
CONTROL GEAR WITH AUTOMATIC
TEST FUNCTION
MINIMUM POWER FACTOR (
λ
)
0.9
Prated/Irated
CONTROL GEAR MAX.TEMPERATURE (tc)
80°C at Q2