background image

Page

 1

 from

 

8

92329300

8

_09_00

2

GENERAL

o

This  device  is  used  indoors 

(

ta  40 C

)

  in  places 

where  emergency  luminaires  are  needed.  Each 
device must be permanently connected to mains 
power  supply

.

  The  GR-292/M/HL/ADR  is 

suitable  for  corridors  lighting  and  the  GR-
293/M/HL/ADR for open area lighting. In normal 
operation  the  battery  is  charging.  In  case    of  a 
mains  power  supply  failure,  the  device  enters 
emergency mode and the illumination LED turns 
on. When the  mains  power  supply is restored, 
the device turns to normal operation.

The  battery  charging  is  completely  controlled

In 

this  case,  is

 

achieved  the  perfect    battery 

maintenance 

as  well  as  the  elongation  of  its 

duration

When  the  battery  has  completely 

charged

it charges with a maintenance current.

The  device  enters  this  mode  when  the  mains 
power  supply  has  failed

 

and  battery  has  lost  its 

Battery Cut-off

Battery Charging

Battery charge failure due to shortcut

The  recharging  device  will  recharge  the  battery 
normally after the short circuit is removed and the 
batterie(s) are reinstalled.

Thank you for your trust in our products  

Olympia Electronics - European manufacturer

ADDRESSABLE SELF TESTING NON-MAINTAINED EMERGENCY CEILING MOUNTED LUMINAIRES

OPERATION VOLTAGE
MAX. SUPPLY CURRENT

220-240V AC / 50-60Hz

19.5mA AC

TECHNICAL CHARACTERISTICS

 

(for LED MODULE specifications see page 8)

 GR-292/M

/

HL/ADR

 GR-293/M/HL/ADR

MAXIMUM POWER CONSUMPTION

4.9W / 5.2 VA

BATTERY

4.8V/4Ah, NiMH (4KRMT 23/62)

U-OUT

6V

  prolonged staring into the luminaire at a distance closer than 0.4m is not expected.

  

E  = 718 lux.

thr

  Do NOT stare at operating light source.The luminaire should be positioned so that 

INSULATION BETWEEN SUPPLY & CONTROL TERMINALS
INSULATION BETWEEN SUPPLY & BATTERY CIRCUIT

Basic insulation

Basic insulation

500V

BATTERY PROTECTION

WORKING VOLTAGE AT WHICH THE INSULATION IS DESIGNED

BATTERY VOLTAGE RANGE

BATTERY CHARGE CURRENT RANGE
BATTERY DISCHARGE CURRENT RANGE

BATTERY SUPPLY CURRENT DURING EMERGENCY

Deep discharge and overcharge protection

4-6V

130 - 200mA (normal charge) / 20 - 30mA (trickle charge)

550 - 730mA

(Vbat=4.8V):650mA

CHARGE TIME

INDICATIONS - CONTROLS

MINIMUM DURATION

LIGHT SOURCE

24 hours

  1 white

 

power LED

Charge, lamp fault, battery fault

TEST button

3 hours

RELATIVE HUMIDITY
CONSTRUCTION MATERIAL

EXTERNAL DIMENSION
WEIGHT

GUARANTEE

Up to 95% 

ABS/PC

3 years

 (1 

year for the battery

)

737gr.

Ø125 x 72 mm

OPERATION TEMPERATURE RANGE

DEGREES OF COVER PROTECTION

PRODUCED IN ACCORDANCE WITH

EMERGENCY ILLUMINATION

IP20

2.3W/760mA

o

5 to 40  C

EN 60598-1, EN 60598-2-22, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3

  330lm 

Controlgear is suitable for LED module only

The controlgear has mains-connected windings of transformer

CONTROL GEAR WITH AUTOMATIC
TEST FUNCTION

MINIMUM POWER FACTOR (

λ

)

0.9

Prated/Irated

CONTROL GEAR MAX.TEMPERATURE (tc)

80°C at Q2

Содержание GR-292/M/HL/ADR

Страница 1: ...ICS for LED MODULE specifications see page 8 GR 292 M HL ADR GR 293 M HL ADR MAXIMUM POWER CONSUMPTION 4 9W 5 2 VA BATTERY 4 8V 4Ah NiMH 4KRMT 23 62 U OUT 6V prolonged staring into the luminaire at a...

Страница 2: ...st button for 10 seconds to delete all the indicated LED errors Then the device enters regular operation mode Pressing the test switch less than 5 seconds will initiate a light source test last for 3...

Страница 3: ...tion can be achieved after that time 1 Untighten the screw and pull up the reflector 7 Mount the luminaire on the ceiling BEWARE of electric shock after reflector removal Plastic base could contain li...

Страница 4: ...suspended ceiling as it is shown bellow Required opening 110mm Step 2 Push up the luminaire as shown in figure 2 Step 3 Continue to push upwards until the lamp locks If you want to pull off the device...

Страница 5: ...2 2 2 2 2 2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3...

Страница 6: ...2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3...

Страница 7: ...ry charge indication LED Figure 4 FAULT LAMP CHARGE BATT GR 292 M HL ADR Escape Route Anti Panic Area GR 293 M HL ADR A 290 BAT 286 mm 31 mm 33 mm TEST Test button TEST TEST TEST 50 mm Address Dipswit...

Страница 8: ...ocuments given by Olympia Electronics or if the buyer modifies the goods provided or has any repairs or re setting done by a third party unless Olympia Electronics has fully agreed to them in writing...

Отзывы: