Detection Circuit #1 (and #2): Test Time Delay Restart
(Continued)
4. Initiate alarm condition by turning DCT switch to “Alarm.”
5. Before the TD1 time delay period expires, push “DELAY/
Reset/Silence” button to restart time delay (3 quick pulses
indicate time is restarted). Time delay #1 restarts to
full programmed delay period. (Restarts may be limited
to 2 restarts or repeated indefinitely based on optional
programming.)
Note: Holding button down does not pause the time
delay.
Note: During TD2 time delay cannot be restarted.
6. Allow System to complete time delay cycles (TD1 and
TD2). During Release Activated* (LEDs and sounder
steady-on) push the “DELAY/Reset/Silence” button.
Verify:
a. Time delay will not restart.
b. Sounder will not silence.
* Red “PUSH to Activate / Alarm When Lit” LED, Red
Shutdown LED, Red Detection 1 LED, and sounder
remain steady-on for 10 seconds.
7. Confirm successful release signal (Pass) on RCT.
8. Return to normal:
a. Reset DCT to normal position.
b. Reset RCT - press reset button.
c. Reset to Normal: Press and hold “DELAY/Reset/
Silence” button for 3 seconds; Green and Red LEDs
are steady-on for 1 second; then Amber LEDs are
steady-on for 1 second; at end sounder quickly pulses
3 times.
After reset, Power LED remains GREEN steady-on.
9. If Detection Circuit #2 is part of the system, repeat Detec-
tion Circuit Tests (listed below) using Detection Circuit #2
in place of Detection Circuit #1. Confirm DCT is in place
of the EOL device on Detection Circuit #2. All figures with
Detection 1 LED indicators will be Detection 2 LED indi-
cators.
Detection Circuit Supervision Test, page 6-7
Detection Circuit Alarm Condition Test, page 6-9
Detection Circuit Test Time Delay Restart, page 6-10
SECTION 6 – OPERATIONAL TEST AND PLACE IN SERVICE
2014-MAY-02 REV. 0 PAGE 6-11
CHECKFIRE 210
Detection and Actuation System
TABLE 6-3: OPERATIONAL TEST (Continued)
009290
RETURN TO NORMAL
STATUS
RESET DCT, RCT, AND
DISPLAY MODULE
POWER LED IS
GREEN STEADY-ON
009290
TEST TIME DELAY
DCT = ALARM
BEFORE END OF TD1,
PUSH BUTTON
TO RESTART TD1
(MAY PUSH BUTTON
MULTIPLE TIMES
IF ALLOWED)
3 PULSES INDICATE
RESTART
009290
COMPLETE TIME
DELAYS
PUSH BUTTON
DURING RELEASE
ACTIVATED (RED
LEDs AND SOUNDER
STEADY-ON)
– VERIFY NO
RESPONSE TO
PUSHING BUTTON
CONFIRM RCT
DISPLAYS “PASS”
Содержание ANSUL CHECKFIRE 210
Страница 2: ......
Страница 6: ...REVISION RECORD PAGE 2 REV 0 2014 MAY 09 NOTES CHECKFIRE 210 Detection and Actuation System...
Страница 12: ...SECTION 1 SYSTEM DESCRIPTION PAGE 1 4 REV 0 2014 MAY 02 NOTES CHECKFIRE 210 Detection and Actuation System...
Страница 26: ...SECTION 2 COMPONENTS PAGE 2 14 REV 0 2014 MAY 02 CHECKFIRE 210 Detection and Actuation System NOTES...
Страница 34: ...SECTION 3 USER INTERFACE PAGE 3 8 REV 0 2014 MAY 02 NOTES CHECKFIRE 210 Detection and Actuation System...
Страница 46: ...SECTION 4 SYSTEM PLANNING PAGE 4 12 REV 0 2014 MAY 02 NOTES CHECKFIRE 210 Detection and Actuation System...
Страница 108: ...SECTION 7 IN CASE OF FIRE PAGE 7 2 REV 0 2014 MAY 02 NOTES CHECKFIRE 210 Detection and Actuation System...